Application
Outdoor or Indoor use.
For use with non-armoured elastomer and plastic insulated cables.
Features
Provides a cable retention seal onto the cables outer sheath.
When used in increased safety applications, this cable gland may be used with braided cable where the braid and the cables outer sheath pass into the enclosure. The braid must be suitably terminated inside the enclosure.
Materials & Finishes
The 501/421 Cable Gland is manufactured as standard in Brass, Stainless Steel and Aluminium.
NPT entries are nickel plated as standard.
Full nickel plating by electroplating or electroless plating is also available, as are other materials on request.
Technical Data
Flameproof Exd and Increased Safety Exe. II 2 GD
Baseefa Certificate No. BAS01ATEX2070X. For sizes Os - F.
Baseefa Certificate No. BAS01ATEX2294X. For sizes G - J.
The above certificates are still current, however they are to be superseded by:
Baseefa Certificate No. Baseefa06ATEX0056X.
IECEx Certificate No. IECEx BAS 06.0013X.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Suitable for use in Gas Groups IIA, IIB and IIC.
Construction and test standards EN 50014,EN 50018, EN 50019 and EN 50281-1-1. IEC 60079-0, IEC 60079-1 and IEC 60079-7.
IP 66, IP67 and IP68 (30 metres for 7 days) ingress protection to IEC 60529, EN 60529 and NEMA 4X.
|
|
Heyco® Liquid Tight Cordgrips
Multi-Hole, NPT Hubs
Features
All accompanying Cordgrips are made of nylon construction with TPE sealing glands that resist salt water, weak acids, gasoline, alcohol, oil, grease, and common solvents. This feature is not assessed by UL.
Locknuts not included. Nylon Locknut Specifications.
For body part dimensions.
Multi-hole glands are only to be used with Heyco Liquid Tight Cordgrips and are not sold separately.
Consult Heyco for cordgrips molded in other colors.
|
|
Metric cable glands, PG, with reducing insert, with cable guide...
Multigum,
Soft plugs,
Metric locknuts,
Metric hex washer faced locknuts,
Slotted plugs,
O-Rings...
|
|
- Available in multiple sizes for cable diameters ranging from .065˝ (1,7 mm) to 1.560˝ (39,6 mm).
- We recommend using the fitting with the smallest maximum diameter that will fit your application.
- Smooth, rounded interior edges for ease of installation.
- Ratchet design of sealing nut assembly provides superior antivibration and ensures a firm grip on the cable.
- Easy to install–no tools required.
- Unique fingers securely lock into a range of panel sizes without use of locknut.
- Rotation prevented when used in “Double D” mounting holes.
- Limited intrusion into enclosure where access is tight.
- Consult Heyco for cordgrips molded in other colors
|
|
|
|
|
|
Conventional methods of chamber entry for validation thermocouples allow only limited numbers of thermocouples to be used. They are relatively time consuming in their application and frequently prone to unacceptable leakage.
The TCEG/1 addresses both these problem areas by providing individual slots for 18 separate thermocouples and a rapid action, locking and securing mechanism.
By utilising a three part sealant arrangement the gland becomes a TCEG/2 with the opportunity of increasing the capacity to 36 individual thermocouples. Should even more thermocouples need to be accommodated, then a ‘Y’ adapter connected to the chamber entry port can double both these quantities.
For mounting onto the autoclave chamber the TCEG is supplied with a Tri-clamp flange with the option of having a 1½” or up to 2½” flange.
The gland body is machined from 316L stainless steel with the cap in CZ121 brass. Sealants are in medical grade silicone to Shore 40 hardness and in accordance with FDA USP Class VI.
|
|
Heyco® Liquid Tight Cordgrips
Multi-Hole, PG Hubs
Features
All accompanying Cordgrips are made of nylon construction with TPE sealing glands that resist salt water, weak acids, gasoline, alcohol, oil, grease, and common solvents. This feature is not assessed by UL.
Locknuts INCLUDED.
For body part dimensions.
Multi-hole glands are only to be used with Heyco Liquid Tight Cordgrips and are not sold separately.
Consult Heyco for cordgrips molded in other colors.
|
|
a whole of frameworks - to weld, seal or screw - make it possible to equip the crossing with the wall;
these frameworks receive modules adapted to the diameter of the conduits and drains;
accessories make it possible to ensure the cohesion and the sealing of the modules installed inside the framework.
|
|
sealing & insulation of the electrical cables by compression of a thermoplastic stuffing. Effective tightening, 2 plates of pressure.
Executions: nickelled brass or polyamide.
|
|
. Press packing evolutionary multicâbles and multipropriétés
. Sealing, fire resistance, to the explosions, the chemicals, the vibrations, the shocks, the rodents, cold, radioactive containment and soundproofing
. Multiple applications
|
|
. Low pressure: from 1 to 7 bars
. Electromagnetic hardening
. Watertightness, with gases and the air
. Fire resistance, to the explosions, the chemicals
. Radioactive containment
. Resistance to the vibrations, the rodents, the cold heat/
. Classification marinades has and H
|
|
MCT was developed for s’ to adapt to any d’ type; environment and to answer the great safety requirements:
firebreak
sealing
acoustic protection
vibrations
behavior with the explosions
resistance to the rodents
version CEM intended for protection against the electromagnetic disturbances.
|
|
Range X-series
System reduced of passage of cables and pipings
for partitions and boxes IP 65-67
|
|
. Reduced system
. IP 65 67
. Personalization with your needs
. Applications: boxes/cases, tables, cupboards, cabins/shelters
. Resistance to the vibrations, the shocks, the rodents, the cold heat/, fire, the products
|
|
| ... products without technical information |
| |
|
|