The Model FL3111HT is a high temperature rated (125°C) ultraviolet (UV) optical flame detector designed to detect unwanted fires while maintaining false alarm immunity. The FL3111HT detects only in the UV spectral range for optimized speed of response.
The FL3111HT's electronics are integral within its stainless steel explosion-proof housing, allowing detector information to be processed at the point of detection. The electronics are fully separated from the Exe wire compartment offering protection during installation and service.
|
|
The Model FL3100H is an Ultraviolet / Infrared flame detector designed to detect fires and provide alarm outputs directly from the detector while maintaining false alarm immunity. It detects fires by monitoring in both the ultraviolet (UV) and infrared (IR) spectral ranges, making it highly immune to false alarms. There is also a hydrogen-specific detector available that detects hydrogen fires.
FL3100 Series flame detectors' electronics are integral within their explosion-proof housings, allowing detector information to be processed at the point of detection. The detectors also provide a 4-20mA stepped output signal indicating detector status. The COPM (Continuous Optical Path Monitoring) self-test feature checks the optical path integrity (window cleanliness) and the detectors' electronic circuitry once every minute.
|
|
|
|
|
|
UV/IR FLAME DETECTOR
Net Safety's Ultra-violet/Infrared ( UV/IR ) flame detector delivers high performance security with functions and features that set it apart. The flame detection reacts to both UV and IR flame radiation delivering accurate and reliable fire monitoring, yet is immune to arc welding, hot body radiation, lightning or sunlight. Two spectrums of radiation must be recognized and confirmed by precisely tuned sensors for the UV/IR to initiate a fire condition, greatly reducing false alarms while providing critical safety performance to your site and personnel.
Enclosed in a rugged, explosion-proof housing, the Net Safety UV/IR flame detectors use the latest in modular microprocessor and UV/IR sensor technology — delivering accurate and reliable monitoring for hydrocarbon fires. It's capable of stand-alone operation or can be connected to a variety of control devices to create a dependable fire monitoring system. The user can define sensitivity and time delay settings and the built-in testing routines ensure continous operation.
The UV/IR Flame Detector has a extra wide field of view - up to 120 degrees, it has one of the lowest power consumption levels available on the market and a wide voltage range - all of these factors can lower your overall cost of ownership during design, installation and power draw requirements. This can add up to thousands of dollars PER DETECTOR over it's installation.
Net Safety has engineered a superior and affordable, UV/IR flame detector that is simple to operate and maintain while delivering all the security and performance required for high-risk, industrial installations!
|
|
The design of this new generation of detectors provides 3 main features :
• Performances
• Guaranteed detection
• Easy installation, use and maintenance.
The efficiency of SIMTRONICS flame detectors offers :
• High sensitivity,
• Very short response time,
• Reliability,
• Immunity from interferences
It also guarantees protection against fire risks in industrial environments and enables the control of fire fighting.
The housings are treated specifically to resist corrosive factors (stainless steel or aluminium housings).
These TV63 UV / 2xIR detectors have a wide viewing angle (110°) and a range higher than 45 m.
The integrated relays and a 4-20mA output enable the control of the TV63 by the control units or by PLC.
The detectors are equipped with an automatic test control, which regularly checks the functionality of detection, as well as the optical and electronic integrity of the system.
The detector’s non-stop auto-tests & intrinsic quality feature SIL 2.
|
|
|
The Model FL4000 is an advanced multi-spectral infrared (MSIR) flame detector designed to provide superior false alarm immunity with the widest field of view. The FL4000 employs a multi-spectral optical IR sensing array with a sophisticated Neural Network Technology (NNT) system to reliably discriminate between actual flames and the vast majority of false alarm sources (such as arc welding). The FL4000 is designed to detect typical fires such as alcohol, n-heptane, gasoline, jet fuels and hydrocarbons. In addition, the FL4000 can see through dense smoke produced by diesel, rubber, plastics and lube oil fires.
|
|
|
|
|
|
PHOENIX TRIPLE IR (MULTISPECTRUM FLAME DETECTOR
Very serious risks to human life, productivity and equipment are always present at industrial facilities that store, transport and process flammable or explosive chemicals. Automatic flame detection and protective action must be initiated within seconds whenever a fire ignites. Net Safety's Phoenix Triple IR Multi-spectrum flame detector provides the reliable and instantaneous flame detection response that is required in high-risk environments while utilizing advanced technologies to reduce false alarm events and provide rock-solid performance in any environment.
The Phoenix will only alarm when input conditions from three distinct IR wavelengths found in fires are satisfied. The Phoenix also incorporates our unique Automatic Digital Zoom (ADZ) technology which provides accurate detection of small and massive flames in the most difficult working situations where other detectors fail. Three precisely tuned IR sensors, ADZ technology, Automatic Visual Integrity, user selectable sensitivity and time delay provide unparalleled false alarm immunity and detection performance.
The Phoenix Triple IR is the ONLY flame detector on the market that does not have an external reflector or light source. Experience has shown that external reflectors and light sources often become obscured by industrial dirt and corrosion which causes unwanted fault alarms that requires difficult and costly maintenance to correct. The Phoenix Triple IR flame detector completely eliminates these issues in applications where salt, dust, petroleum vapor, heavy rain, snow or blowing sand are present.
|
|
The design of this new generation of detectors provides 3 main features :
• Performances
• Guaranteed detection
• Easy installation, use and maintenance.
The efficiency of SIMTRONICS flame detectors offers :
• High sensitivity,
• Very short response time,
• Reliability,
• Immunity from interferences
It also guarantees protection against fire risks in industrial environments and enables the control of fire fighting.
The housings are treated specifically to resist corrosive factors (stainless steel or aluminium housings).
These TV63 detectors have a wide viewing angle (110°) and a range higher than 85 m.
The integrated relays and a 4-20mA output enable the control of the TV63 by the control units or by PLC.
The detectors are equipped with an automatic test control, which regularly checks the functionality of detection, as well as the optical and electronic integrity of the system.
The detector’s non-stop auto-tests & intrinsic quality feature SIL 2.
|
|
|
|
|
|
ULTRAVIOLET FLAME DETECTOR
Net Safety's Single UV flame detector reacts to the ultraviolet radiation found in hydrocarbon fires, delivering accurate and reliable fire monitoring. The Single UV does not react when exposed to incandescent or fluorescent lighting, heaters or sunlight - meaning false alarms are virtually eliminated..
Enclosed in a rugged, explosion-proof housing, the Single UV uses the latest in microprocessor and UV sensor technology. It is capable of stand-alone operation or can be connected to a variety of control devices to create a dependable flame monitoring system. The user can define sensitivity and time delay settings to virtually eliminate false alarms and the built-in testing routines ensure continuous operation.
The Single UV has a Field of View of up to 120 degrees and is available with analog or analog/relay output configuration for 12 or 24 VDC systems - just let us know your requirements!
Net Safety's Single UV flame detector is globally certified Class I, Division 1 for hazardous locations to CSA, ATEX, Factory Mutual (FM), ANSI-UL/ISA, INMETRO, and GOST-R performance, technical and safety standards.
Net Safety has engineered a cost effective, high-performance flame detector, ideal for even the most high-risk, industrial applications!
|
|
Dräger Safety optical flame detectors provide the reliable detection of a wide range of both hydrocarbon and non-hydrocarbon based fires. Providing a perfect solution to the ever increasing demand of flame detection throughout industry, they can also be used along with Dräger gas detection technologies to form part a complete safety system
The reliability and flexibility of Dräger flame detectors, along with their worldwide approvals ensure suitability for just about any application anywhere in the world.
|
|
uv1a3
Specifications:
- Optical range: 190-270 nm
- Supply voltage: 560 VAC
(supplied by control)
- Mounting threads: 1/2" NPT
- Operating temperature: -40°C to 94°C
(-40°F to 200°F)
- Available in NEMA (Class 1, Div 2,
Group C and D) and Cenelec
approved explosion proof housing
(EEx d IIC T6)
|
|
AIE-EA, Ionization Smoke Sensor
STANDARD FEATURES
Uses the noise immune Digital Communication Protocol (DCP), which utilizes interrupts for fast response to fires
Built in fire test feature
Automatic compensation for sensor contamination
Simple and reliable device addressing method
Low Profile - Only 2.22" high, including base
|
|
95ir/95uv/95ds insight scanners
The Fireye InSight Type 95IR, 95UV, and 95DS flame scanners are microprocessor based flame scanners utilizing solid state infrared (IR), ultraviolet (UV) or dual (IR and UV) sensors.
|
|
HF-24, Ultraviolet Flame Detector
STANDARD FEATURES
Detects fast flaming fires
Highly reliable, long life UV receptor tube
Low power consumption
HF-24 can be intermixed with other types of detection on the panel's detection circuitry
Interchangeable with Hochiki America's standard smoke and heat detector bases
Size and color similar to other Hochiki America smoke and heat detectors
Easily maintained: cleaning can be accomplished without disassembling the detector
Not UL-listed
|
|
| ... products without technical information |
| |
paragon
TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer. Paragon scanner provides high integrity sensing of multiple flame properties, including Amplitude, Flicker Frequency and Flame Learned vs. Stored Curve Fitting.
|
|
|
|
|
|
WINDOW 141 FLAME SCANNING SYSTEM
The PIA WINDOW 141 flame scanning system uses proven flame scanning technology which combines a simultaneous UV and IR detection, with the latest flash memory microcontroller.
The system includes:
A single scanner head having a combination of UV tube (ultraviolet), a high speed IR cell (infrared), and a window which allows a direct visual sight to the scanned flame through the same hole used by the sensors. It can detect coal, oil, gas and other non standard fires.
A signal processing module handling independently both UV and IR signals received from the scanner head. It displays absolute frequency counts and the strength (relative to adjustment) of UV and IR signals. A flame strength output of 0-20mA or 4-20mA, UV and IR flame on relays, and a fault relay transmit their data to your burner management system.
A chassis (mounting rack) providing termination hardware for all the wiring and 1 to 8 slots to quickly plug and remove the scanner modules.
A plug in data terminal DT-1 to program and diagnose the signal processing module, so only the operator having the DT-1 can modify
the module adjustments.
An optional FS-2 flame source to simulate an adjustable flame signal containing UV and IR light for testing the system on the field.
|
|
A combination of independant UV (ultraviolet) and IR (infrared) flame detection plus a direct visual sight to the scanned flame in a single scanner head.
The advantages of the WINDOW 141 head are:
Pure UV detection (220nm peak): not affected by visible and sunlight radiations like a Si UV enhanced system would.
IR detection (1 550nm peak) very stable: not affected by visible radiations and temperature variations like for the Ge, PbS or other IR cells.
For easy installation, a ball swivel mounting on the burner front allows adjustment of the viewing angle. Standard 1'' NPT connections are used for the ball swivel and scanner head.
The visible section of the radiation is only for visual observation through the WINDOW (patented).The following can be observed:
Sight alignment
Flame quality
Lens cleanness
Operation of the shutter
Inside UV and IR LEDs
|
|
A combination of independant UV (ultraviolet) and IR (infrared) flame detection plus a direct visual sight to the scanned flame in a single scanner head.
The advantages of the WINDOW 141 head are:
Pure UV detection (220nm peak): not affected by visible and sunlight radiations like a Si UV enhanced system would.
IR detection (1 550nm peak) very stable: not affected by visible radiations and temperature variations like for the Ge, PbS or other IR cells.
For easy installation, a ball swivel mounting on the burner front allows adjustment of the viewing angle. Standard 1'' NPT connections are used for the ball swivel and scanner head.
The visible section of the radiation is only for visual observation through the WINDOW (patented).The following can be observed:
Sight alignment
Flame quality
Lens cleanness
Operation of the shutter
Inside UV and IR LEDs
|
|
Flame detector for continuous operation IFW 50
Flame detector for flame signalling or for multi-flame control in conjunction with IFD 450/454, for continuous operation, ionisation control.
Mains voltage: switchable from 220/240 V AC to 110/120 V AC, for earthed or unearthed mains.
Flame detector IFW 15
Flame detector for flame signalling or for multi-flame control in conjunction with IFS 110/111IM, for intermittent operation, ionisation or UV control. For earthed or unearthed mains, mains voltage:110/120 V AC or 220/240 V AC.
Flame detectors PFF
Flame detector in 19" standard rack for multi-flame control in conjunction with PFS/PFD or for flame signalling.
PFF 704: for intermittent operation, ionisation or UV control,
PFF 754: for continuous operation, ionisation control,
with 4 independent flame amplifiers,
mains voltage: switchable from 220/240 V AC to 110/120 V AC, for earthed or unearthed mains.
|
|
Compact Flame Monitor D-LX 100
Self-monitoring and fail-safe compact flame monitor for the monitoring of gas, oil and coal flames with integrated UV, VIS or IR flame sensor, primarily in single burner furnaces
Features
Suitable for continuous operation and 72-hour operation according to TRD 604
Compact design, flame sensor and control unit in one enclosure, takes up no space in control cabinet
LED display for settings and operational status
ATEX approved (D-LX 100 Ex)
Applications
Power stations
Chemische Industrie
Refineries
Cement plants
Waste incinerators
Steam generators
Heating plants.
|
|
Infra-red Flame Monitor D-IR 55
Infra-red flame monitor for intermittent operation.
Analyses flame intensity (flickering) in conjunction with the D-LE 55 ISF-CG flame sensor
Features
monitoring of gas and oil burners of any load
suitable for intermittent operation
simple installation on TS 35 DIN-rail
Application
Chemical industry
Refineries
Cement plants
Waste incinerators
Steam generator
Heating plants
|
|
UV Flame Monitor D-UV 55
UV flame monitor for intermittent operation.
Analyses the flame intensity in conjunction with the D-LE 55 UL-CG flame sensor
Features
monitoring of gas and oil burners of any load
suitable for intermittent operation and continuous operation (only D-IO 55-20)
simple installation on TS 35 DIN-rail
Applications
Chemical industry
Refineries
Cement plants
Waste incinerators
Steam generators
Heating plants
|
|
|
|
|
|
The self-checking SAFYR PACKSCAN flame detectors are designed for monitoring solid or liquid fuel burners (oil, pulverised coal, heavy liquid residues). They are adapted for multi-burner installations by facilitating flame discrimination.
A binary safety signal is transmitted in the presence or absence of a flame. The output signal is also available on terminals for recording or remote display purposes.
Operation of the SAFYR PACKSCAN flame detector is based on the characteristic flickering phenomena of flames, generally between 0 to 150HZ. It uses a silicium photodiode cell, adapted to the combustion frequency in the visible light band (320 to 1100nm).
A display indicates all the configured parameters, as well as the detection level.
30 years of experience in the field of flame detection gives the SAFYR PACKSCAN the following advantages :
• An ‘all in one concept’ with an integrated amplifier in the scanner head for easy installation.
• Two microprocessors for increased safety and reliability.
• Approved by APAVE to meet all safety criteria requirements
• Detection level indicator to simplify commissioning
• Various standard confi guration methods by internal switches, by remote and by serial link, to simplify configuration
• Two SPDT output switches to indicate flame presence and proper detector operation
|
|
|
|
|
|
The self-checking RUBY PACKSCAN flame detectors are mainly designed for monitoring gas burners.
They transmit a binary safety signal on the presence or absence of a flame.
The response time to a flame shutdown is less than 1 second, as per Standard EN298 relating to gas safety equipment.
The RUBY PACKSCAN detector uses a detection tube for ultraviolet wavelengths between 185 and 280nm.
An auto-checking mechanism for the tube covers the sight hole three times per second in order to ensure self checking operation.
A display enables visualisation of the configured parameters as well as the level of detection.
30 years in the field of flame detection gives the RUBY PACKSCAN the following advantages :
• an ‘all in one concept’ with an integrated amplifier in the scanner head for easy installation
• two microprocessors for increased safety and reliability
• Approved by APAVE meeting all safety criteria requirements.
• Detection level indicator to simplify commissioning
• Various standard confi guration methods by internal switches, by
remote and serial link to simplify configuration.
• DPDT output switch to indicate flame presence and proper detector operation.
|
|
| ... products without technical information |
| |
| ... products without technical information |
| |
|
|