Differential pressure transducer
1/8", max. 12 bar
AirCom Pneumatic
The differential pressure between port H and L is converted into a proportional, electrical signal by a
silicon pressure transducer, amplified and then monitored as an analogue voltage or current signal.
Media: compressed air or non-corrosive gases
Supply_voltage: 12...32 V DC, residual ripple 5%, with voltage protection
Electrical_connector: plug M12x1, 4-pin, optionally 4-wire connection cable
Output_signal: 4...20 mA: max. power consumption 260 mW, 1...6 V: max. power consumption 60 mW
Linearity/Hysteresis: < 0.1% FS typ., < 0.25% FS
Repeatability: < 0.1% FS typ., < 0.5 % FS
Long-term_stability: < 0.2% FS typ., < 0.5 % FS
Temperature_sensitivity:
< 0.02% FS typ. per °C at 0 to 50 °C / 32 to 122 °F
< 0.16% FS typ. per °C at 0 to 50 °C
Response_time: 1 ms for 10...90% of pressure range
Shock_resistance: 50 g
Vibration_resistance: 10 g at 5...500 Hz
Protection_class: IP 67 with plug mounted
Mounting_position: any
Temperature_range: -25 °C to 85 °C / -13 °F to 185 °F
Body: aluminium
silicon pressure transducer, amplified and then monitored as an analogue voltage or current signal.
Media: compressed air or non-corrosive gases
Supply_voltage: 12...32 V DC, residual ripple 5%, with voltage protection
Electrical_connector: plug M12x1, 4-pin, optionally 4-wire connection cable
Output_signal: 4...20 mA: max. power consumption 260 mW, 1...6 V: max. power consumption 60 mW
Linearity/Hysteresis: < 0.1% FS typ., < 0.25% FS
Repeatability: < 0.1% FS typ., < 0.5 % FS
Long-term_stability: < 0.2% FS typ., < 0.5 % FS
Temperature_sensitivity:
< 0.02% FS typ. per °C at 0 to 50 °C / 32 to 122 °F
< 0.16% FS typ. per °C at 0 to 50 °C
Response_time: 1 ms for 10...90% of pressure range
Shock_resistance: 50 g
Vibration_resistance: 10 g at 5...500 Hz
Protection_class: IP 67 with plug mounted
Mounting_position: any
Temperature_range: -25 °C to 85 °C / -13 °F to 185 °F
Body: aluminium
-
zoom