ATX
Group: EGS Electrical

Safety lighting: emergency exit
FNES series ATX

  • safety lighting: emergency exit FNES series ATX
Self-Contained Emergency Lighting with Self-Test System - Zone 2 - 21 & 22

Applications:
• Provides adequate lighting and/or visual indication of access and
exit routes during an evacuation in a hazardous environment.
• Can be installed in hazardous areas designated as Zone 2, 21
and 22.
• Typical applications include oil refineries, petrochemical plants,
pulp, paper mills and silos.
Features:
• Power supply 230 Vac 50/60 Hz.
• 1 hour duration.
• Non-maintained.
• Operates in any position.
• 1 x 8 W fluorescent or 2 x 3 W incandescent lamp versions
(lamps
supplied).
• Open and close using an Allen key (size 10) or a 6 mm flat
screwdriver.
• Connection to plug-in terminal block via 2 x 5 x 2.5 mm2
terminals.
• Two M20 clearance holes supplied with one cable gland
(dia. 6.5 to 14.5 mm), one blanking plug and two locknuts.
• Charge indicator by 4 nos yellow LEDs (lifetime over 10 years).
• Automatic built-in self-test system (SATI) with memorization of
tests indicated by LEDs .