Chint Electric Co.,Ltd.
Group: Chint

SF6 gas insulated high-voltage instrument transformer
110 - 126 kV Chint Electric Co.,Ltd.

SF6 Voltage Transformer (Outdoor)

Application: for power, voltage measurement and relay protection in voltage up to 126kV AC 50Hz power system.

Standards: IEC 60044-2
Ratings: 110kV-126kV.

Features:
 Reliable operation
 Reliable insulation capability
 High measurement accuracy
 Maintenance-free
 Reliable sealing performance

Technical Data:
 Model: JDQXF-110W2
 Rated primary voltage: 110√3
 System nominal voltage (kV): 110
 Highest voltage for equipment (kV): 126
 Rated voltage ratio (kV): 110/√3 /0.1/√3 /0.1/√3 /0.1kV
 Accuracy classes: 0.2/0.5/3P
 Rated output (VA): 100/200/300
 Partial discharge level (pC): ≤5
 Short time power frequency withstand voltage (kV/1min): 200
 Lightning impulse withstand voltage (kV): 480
 Internal insulating medium: SF6 Gas
 Creepage distance (mm): ≥3150
 Dimensions (mm): 680x670x1920
 Gross weight (kg): 450

* All the data are only examples for your reference.