SF6 gas insulated high-voltage instrument transformer
110 - 126 kV
Chint Electric Co.,Ltd.
SF6 Voltage Transformer (Outdoor)
Application: for power, voltage measurement and relay protection in voltage up to 126kV AC 50Hz power system.
Standards: IEC 60044-2
Ratings: 110kV-126kV.
Features:
Reliable operation
Reliable insulation capability
High measurement accuracy
Maintenance-free
Reliable sealing performance
Technical Data:
Model: JDQXF-110W2
Rated primary voltage: 110√3
System nominal voltage (kV): 110
Highest voltage for equipment (kV): 126
Rated voltage ratio (kV): 110/√3 /0.1/√3 /0.1/√3 /0.1kV
Accuracy classes: 0.2/0.5/3P
Rated output (VA): 100/200/300
Partial discharge level (pC): ≤5
Short time power frequency withstand voltage (kV/1min): 200
Lightning impulse withstand voltage (kV): 480
Internal insulating medium: SF6 Gas
Creepage distance (mm): ≥3150
Dimensions (mm): 680x670x1920
Gross weight (kg): 450
* All the data are only examples for your reference.
* Customized products are available according to your requirements.
Application: for power, voltage measurement and relay protection in voltage up to 126kV AC 50Hz power system.
Standards: IEC 60044-2
Ratings: 110kV-126kV.
Features:
Reliable operation
Reliable insulation capability
High measurement accuracy
Maintenance-free
Reliable sealing performance
Technical Data:
Model: JDQXF-110W2
Rated primary voltage: 110√3
System nominal voltage (kV): 110
Highest voltage for equipment (kV): 126
Rated voltage ratio (kV): 110/√3 /0.1/√3 /0.1/√3 /0.1kV
Accuracy classes: 0.2/0.5/3P
Rated output (VA): 100/200/300
Partial discharge level (pC): ≤5
Short time power frequency withstand voltage (kV/1min): 200
Lightning impulse withstand voltage (kV): 480
Internal insulating medium: SF6 Gas
Creepage distance (mm): ≥3150
Dimensions (mm): 680x670x1920
Gross weight (kg): 450
* All the data are only examples for your reference.
* Customized products are available according to your requirements.
-