Torque limiter COLMANT CUVELIERApplications of Intensity Detector Relay :
- Engine circuit breaker : overtorque engine, jammed conveyor, overloaded winch... - Load regulation : grinding machine, conveyor belt... Our Intensity Detector Relays include all the options for a universal usage : * Sensitivity : from 1 mA to 10 A (to be used with an intensity transformer from 4 A) * Direct or 50 Hz alternating current * Memorised circuit breaker or timed reset * Intrinsic safety (direction of relay : NO or NF) * Over or under intensity threshold - Starting tempo - Peak tempo * 2 outputs 1 RT General characteristics - Case to be clipped on W rail. - Material : black and white Noryl. - Dimensions : 45 x 85 x 75 mm. - Maximum temperature : from -10 to +55°C - Factor of usage : 100% - IP 40 - Terminal with 4mm screws - Unlosable screws delivered untight. - Power (<2VA - 48..63Hz) : 24 Vcc or 24 vac, 115 vac or 230 vac +/- 15% and with an isolation transformer (VDE0551), voltage : maxi +/- 15% & green led alim. - Relay output : 230 vac - 5 A & orange led action. - Start tempo : 0 to 10 sec. - Peak tempo : 0 to 5 sec & orange led. - Tempo R to Z < 100 ms. - In compliance with European ‘CE’ standards. |