Control of emergency stops
Safety management in a compact 22.5 mm format
Mono or two-channel with wiring. "Low consumption" Inputs
Removable terminals
Performance level with AWAX controller: PL = d
Safety category: 3 (two-channel)
Safety Integrity Level: SIL 2
Time before dangerous failure: MTTFd = 240 years
Cycle before dangerous failure: B10d=100,000 at 5A
Risk duration: 20 ms max.
Cable severing protection: yes (opening of safety lines)