Air-cooled diesel engine generator set
13 kVA | EMZ-13 ELECTRA MOLINS


The "Emergency Service" power is applicable for generators that operate in the event of a mains outage. This power rating cannot be exceeded.

The "Main Service" power is applicable for generators that operate as the main source of electrical power. This power rating can be exceeded by 10% for limited periods of time (maximum: 1 hour every 12 hours).

However, to prolong diesel engine life, we recommend that the mean active power (kW) connected to the generator in a 24-hour period not exceed the following values:

For mains-failure emergency service, 80% of emergency power.
For main service, 70% of main-service power.