Model: EMJ-200
Form of Construction: Soundproof or Automatic Soundproof
Control panel type AUT-MP12
Diesel engine JOHN DEERE 6068HF258
Alternator LEROY SOMER LSA 462 M3
Output in standby service on mains failure
(LTP "Limited Time Power" according to norm ISO 8528-1)
200 kVA 160 kW
Output in prime service
(PRP "Prime Power" according to norm ISO 8528-1)
180 kVA 144 kW
Current intensity in standby service on mains failure 289 A
Triphasic voltage 400 V
Voltage precision in steady state ±0,5%
Frequency 50 Hz