General Cable
Group: General Cable

Electric power supply cable: thermoplastic
12 / 20 kV | VULPREN General Cable

CONDUCTOR
Aluminium, semi-rigid class 2
INSULATION
High-modulus ethylen-propylene 105ºC (HEPR)
SCREEN
Copper wire helicoidal layer
SHEATH
Halogen-free thermoplastic polyolefine

VOLTAGE
12/20 kV

STANDARDS
IBERDROLA NI 56.43.01- Design standard
EN 50267 - Halogen free. Low corrosivity and acidity of evolved gases
IEC 60754 - Halogen free. Low corrosivity and acidity of evolved gases


APPLICATIONS AND MAIN CHARACTERISTICS
Cables for power distribution for medium voltage outdoor, cased or underground installations.

Abrasion and tear-resistant jacket. Easier slide.

Reticulating process: The three extruded layers (semi-conductors and insulation) are extruded at the same time in a triple head. The tube is kept under controlled inert gas (N2) pressure to prevent the formation of vacuoles. The temperature profile of the tube is carefully controlled to ensure the correct level of reticulation in the cable core.

Halogen-free cable.
  • zoom



standListOtherProduct www di En 2012-05-22-31