AC/DC power supply / ATEX / DIN rail
BXNT(I), BXLT(I) series GEORGIN S.A.

{{requestButtons}}

Characteristics

  • Type:

    AC/DC

  • Other characteristics:

    ATEX, DIN rail

  • Input voltage:

    230 V

  • Current:

    4 mA, 20 mA

Description

This device is designed to interface 4/20mA signals coming from the hazardous to the safe area.

Input: 4/20mA 2 wires active or passive
Output: 4/20mA 2 wires active or passive
Supply: 24-48 VDC, 110 VAC or 230 VAC
Model: 1 or 2 channels and signal duplicator (1 input – 2 outputs)
Setting: Adjustment potentiometer for the source and the curve on the front
green LED for presence of voltage
Installation : Safe area

Options:
» Hart signal transparency with the barrier (BXNTI – BXLTI - BXMTI)
» Screw terminals
» ACCDIVBX power supply cables
» Ex d enclosure - RTPE9-DIN or other Ex d enclosure

EC Type examination certificate number :
LCIE 02 ATEX 6104X

IECEx conformity certificate :
LCI 09.0013X

ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]