Universal signal converter LX series
galvanically-isolated

universal signal converter
universal signal converter
Add to favorites
Compare this product
 

Characteristics

Signal type
universal
Other characteristics
galvanically-isolated

Description

This card is designed to interface and convert RTD100, linear resistor, thermocouples or potentiometer signals coming from the hazardous to the safe area. Input: » LXR: RTD100 with fixed scale to be defined according codification » LXC: Thermocouple with fixed scale and type to be defined according codification » LXP: Potentiometer from 0-1kOhm to 0–50kOhm Output: Current (4/20mA - 0/20mA…), Voltage (0/5V - 0/10V…) or other on request Supply: 24 VDC, 48 VDC, 110 VAC or 230 VAC Model: 2 channels Setting: Adjustment potentiometer for the source and the curve green LED for presence of voltage Installation : Safe area Options: » With or without keying pin EC Type examination certificate number : LCIE 02 ATEX 6431X ATEX/IECEx classification : II (1) GD [Ex ia] IIC ou [Ex ia] IIB ou [Ex iaD]

Catalogs

No catalogs are available for this product.

See all of GEORGIN S.A.‘s catalogs

Exhibitions

Meet this supplier at the following exhibition(s):

ACHEMA 2024
ACHEMA 2024

10-14 Jun 2024 Frankfurt am Main (Germany)

  • More information