Compensation tank for refrigeration circuit
ø 3" - 20" | S-80 series
Henry Technologies
Receivers
We manufacture a complete line of both Horizontal and Vertical liquid refrigerant receivers. Sizes range from 3" to 20" diameter. Receiver storage capacities are based on the liquid occupying no more than 90% of the internal volume when the temperature of the refrigerant is 90°F (32°C) per ASHRAE Standard 15-78.
Receivers should be selected based on the operating charge for all system components, including the liquid lines. It is usual to add a small percentage to cover the refrigerant in long runs of suction and discharge lines, etc. It is essential that the maximum operating charge be determined, e.g., winter chargein air cooled condenser having flooded head pressure control, this being much greater than the normal summer charge. We are certified by the National Board of Boiler and Pressure Vessel Inspectors.