HCP-1008E, 8-Zone Expandable Fire Alarm Control Panel

STANDARD FEATURES
8 Class B (Style B) Initiating Circuits which may be configured as 4 Class A (Style D) Circuits. Expandable up to 24 Class B or 12 Class A Initiating Circuits.
4 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.7 Amps max. per circuit)
Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audible may be configured as Steady, Temporal Code, California Code or March Time.
Each Initiating Circuit can be configured as Alarm, Supervisory, Waterflow or Trouble
Two outputs for 4 wire resetable smoke power supply (200 mA max. each)
Alarm verification on Initiating Circuits
Easy configuration via push buttons and SLIDE switches on the front panel