loading in progress... Please wait

www.lgis.com
Selected product 
vacuum circuit breaker

Vacuum circuit breaker


1. General
1) High reliability of the operating mechanism
- Separate design of the main circuit from the operating mechanism.
- Adopt the toggle link method.
- Improved the reliability of electric circuit.
- Adopt the rapid auto-reclosing method as a standard option. (O-0.3sec.-CO-3min.-CO)
2) High interrupting performance
- Make short of the interrupting time. (3cycles)
- Increase the rated short-circuit withstand characteristics. (1sec. to 3sec.)
3) Great operational safety
- Reinforce the insulation in the conduct, by adopting the molded housing in each phase.
- Built in the device making the contacts open first when draw in and out.
- Adopt the tulip-shape connection between the cradle and the VCB.

2. Type: LVB
3. Ratings
- Rated voltage: 7.2kV, 12kV, 17.5kV, 24kV
- Rated normal current: 630A, 1250A, 2000A, 2500A
- Rated short-time withstand current: Max. 40kA
4. Wide range of accessories (optional)
5. Applied standard: IEC 62271-100 (M2, E2(List1), C2 class)
6. Certification: KEMA, KERI


More specifications...

Other products from -

LS Industrial Systems

 
back

soc-pmea www di En 2009-11-47-22