Phase control relay riese electronicother attributes
This device monitor controlles a 3-
other
phase net for correct phase
attributes
sequences and total failure of the
phases. It operates according to
the closed-circuit current principle
and hence monitors itself.
Therefore, it is guaranteed that in
case of a malfunction of the
system it will shut down save. If
all phases are in the right position
the output relay puts through, the
contact 11-14 is closed. In case
of incorrect phase or phase
failure the relay drops out. The contact 11-12 is closed. Even a
faulty fuse is recognized as a
phase failure, if no voltage is fed
back to the measuring relay by
the user. The pick-up time in the
case of an incorrect phase
position is 70 ms, the drop-out
time 40 ms. The air gaps and
leakage paths of the test circuit
were sized according to the VDE
0110C, 550 V AC, those of the
output circuit designed according
to VDE 0110C, 250 V AC.
|