Analog temperature control unit TST01M
thermoelectricfor solar collectors

analog temperature control unit
analog temperature control unit
analog temperature control unit
Add to favorites
Compare this product
 

Characteristics

Display
analog
Type
thermoelectric
Use
for solar collectors
Maximum temperature

Min.: -10 °C
(14 °F)

Max.: 50 °C
(122 °F)

Description

ANALOG SOLAR CONTROLLER - ELIOS BASIC Differential analog solar controller-Elios Basic for solar heating plants: it compares temperatures of fluids in the collectors and the storage tanks and, when the difference is greater than DeltaT, starts the heat exchange through the pump. 3 temperature inputs from NTC sensors and 2 on-off relay outputs SPST. Additional thermostat for driving auxiliary heat source. LEDs show presence of power and pump activity. Configuration of 5 different system layouts. Adjustable antifrost function. TECHNICAL FEATURES Power supply 230V ~ -15% +10% 50Hz Sensor NTC 10Kohm @25°C ±1% Power absorption 2,3VA Pump output 5(1)A@250V~(powered) Integration output 5(1)A@250V~(powered) Accuracy ±1,5°C Green LED indicator Power supply Red LED indicator Pump active Protection grade IP30 Operating temperature range0°C .. 40°C Storage temperature range -10°C .. +50°C Humidity limits 20% .. 80% non-condensing Case ABS VO self-extinguishing Dimensions H87 W132 D37mm
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.