The FC121-ZA is a conventional fire control panel with an integrated operating unit for 2 zones. The control unit has been designed to be very simple to use while offering exceptional flexibility via a comprehensive feature list. The FC121-ZA is ideally suited for small applications, e.g. in schools, shops, hotels. Expansions and accessories must be ordered separately.
Mains voltage
AC 196...253 V
Operating voltage
DC 21…28.6 V
Power supply
25 W
Operating current
900 mA
Bypass time for emergency power supply
72 h
Battery capacity
2x 12 V / 4 or 7 Ah
Operating temperature
-5…40 °C
Relay outputs
1x dialer fault
Monitored output
1x sounder line , 1x dialer fire
Programmable inputs
2
Plug-in position
1
Zones
2
Conventional devices per zone
Max. 32
Relative humidity
≤95 % rel. (no condensation)
Storage temperature
-20…+60 °C
Protection category
IP30
Color housing/cover
Gray, ~RAL 000 50 00
Dimensions (W x H x D)
310 x 360 x 85 mm
Dimensions (W x H x D)
310 x 360 x 85 mm
Weight (net)
2.79 kg