4 analog inputs with IEPE interface
Signal conversion in frequency range of 31 mHz to 20 kHz (16 bits)
Max. sampling rate 50 kSPS
5 µs offset between channels
Condition Monitoring
For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.
Performance Data
Supply voltage -
+24 V DC (+18-30 V DC)
IEPE Interfaces
Type -
IEPE interface
Amount -
4
Measurement range -
±0.172 ... ±5.5 V AC
Resolution -
16 bits
Conversion rate/channel -
≥ 5 µs (adjustable, default setting 5 µs)
Data recording/channel -
maximum 64 Word
Short-circuit proof, current limited -
Yes
Cable break monitor -
Yes
Hardware filter -
typically 31 MHz (high pass 1st order), typically 20 kHz (low pass 3rd order)
Software Band Pass Filter
Lower frequency limit -
adjustable (minimum 0.1 Hz)
Upper frequency limit -
adjustable (maximum 10 kHz)
Processed measured values/cycle -
configurable
Output parameters -
Average Value, Minimum Value, Timestamp, Minimum Value, Timestamp, Maximum Value
Sensor Supply
Adjustable current -
0, 4, 8, 12 mA individually adjustable for each channel
Supply voltage -
+18-30 V DC
Sensor voltage -
typically 19.1 V DC
Mechanical Features
Dimensions -
12.5 x 104 x 72 mm (W x H x D)