Diaphragm operated differential pressure switch
5 kPa | LF32
Zhejiang Lefoo Industrial Co.,Ltd
LF32 switch is capable to sense tiny pressure change and widely used to control the flue of aerator, to monitor fan and air conditioner. It is also suitable for over heating protection and frost protection in industrial cooling system. Due to its outstanding design, the setpoint can be adjust visually.
Series No.
LF32
Media
Air, non-combustible and non-aggressive gasses
Max Operating Pressure
5 kPa
Mounting position
Diaphragm in any vertical plane
Degree of protection
IP54 (with cover)
Operating Temperature
-40° C to 85° C
Contact Arrangement
SPST or SPDT
Electrical Rating
Resistance: Initial: <400 milliohms;
1.5A (0.4A) @ 250V
Terminals
6.4 mm(0.25") copper alloy
Connection
6.0mm Dia. for tube connection
Model
Pressure Range
Differential
Tolerance
LF32-02
20 ~ 200 Pa
10 Pa
/-15%
LF32-03
30 ~300 Pa
10 Pa
/-15%
LF32-04
40 ~400 Pa
20 Pa
/-15%
LF32-05
50 ~ 500 Pa
20 Pa
/-15%
LF32-10
200 ~ 1000 Pa
100 Pa
/-15%
LF32-25
500 ~ 2500 Pa
150 Pa
/-15%
Conversion: 1"W.C.= 1 inch/H2O=249Pa 1mbar=100Pa
Series No.
LF32
Media
Air, non-combustible and non-aggressive gasses
Max Operating Pressure
5 kPa
Mounting position
Diaphragm in any vertical plane
Degree of protection
IP54 (with cover)
Operating Temperature
-40° C to 85° C
Contact Arrangement
SPST or SPDT
Electrical Rating
Resistance: Initial: <400 milliohms;
1.5A (0.4A) @ 250V
Terminals
6.4 mm(0.25") copper alloy
Connection
6.0mm Dia. for tube connection
Model
Pressure Range
Differential
Tolerance
LF32-02
20 ~ 200 Pa
10 Pa
/-15%
LF32-03
30 ~300 Pa
10 Pa
/-15%
LF32-04
40 ~400 Pa
20 Pa
/-15%
LF32-05
50 ~ 500 Pa
20 Pa
/-15%
LF32-10
200 ~ 1000 Pa
100 Pa
/-15%
LF32-25
500 ~ 2500 Pa
150 Pa
/-15%
Conversion: 1"W.C.= 1 inch/H2O=249Pa 1mbar=100Pa
-
zoom