High-performance power controller
To adjust the power of high/low temperature coefficient heating elements
FUNCTION -
2PX as 2 1PX, 3PX as 3 1PX
DIMENSIONS -
L x H x D from 150 x 320 x 232 to 593 x 1094 x 474 mm depending on the power size, equivalent to THP
INPUTS -
0/4…20 mA, 0/1…5 V, 0/2…10 V
CONTROL -
V voltage, V² voltage, I current, I² current, P power
COMMUNICATION -
RS 232, slot for modules, USB, I/O bus
POWER CIRCUIT CONNECTIONS -
Single-phase (1P), three-phase with two controlled phases (2P), three-phase with three controlled phases (3P)
RATED CURRENT (A) -
500 V: 16, 37, 75, 110, 130, 170, 280, 350, 495, 650, 780, 1000, 1500 (3P: 1850, 2600), (2P: 2000, 2750),(1P: 2100, 2900), 690 V: 80, 200, 300, 500, 780, 1400 (3P: 1700, 2200), (2P: 1850, 2400), (1P: 2000, 2600)
RATED VOLTAGE -
P500: 230 -20%… 500 +10%, P690: 500 -20%… 690 +10%
LOAD TYPE -
Resistors with low or high temperature coefficient (RC / RF up to 20), transformers, inductive loads
SAFETY -
7 easy access LEDs, Anomaly indication: via LED, 3 alarm relays and Thyro-Touch keypad, Load diagnostic
OVERALL ACCURACY -
±0.5%
LIMITATIONS -
Veff voltage, Ieff current, P power, Ipeak (MOSI)
STARTING MODE -
RAMP, sofstart-sofdown, MOSI (high temperature coefficient)
FUNCTIONING MODE -
Wave trains (TAKT), phase throttling (VAR), sequential voltage control with phase angle (VSC_VAR)
ANYBUS MODULES -
Modbus RTU/TCP, PROFIBUS DPV1, PROFINET, DeviceNet, EtherNet/IP, EtherCAT
DASM MODULE -
optional (2 RJ-45 connectors): network load optimization for multiple wave train THPX (TAKT)