Earth-leakage protection relay P50EFR
SPDTIECadjustable

earth-leakage protection relay
earth-leakage protection relay
Add to favorites
Compare this product
 

Characteristics

Measured/monitored value
earth-leakage
Contact configuration
SPDT
Other characteristics
IEC, adjustable, time delay, compact, panel-mount
Tripping current

Min.: 0.1 A

Max.: 2 A

Description

• Earth Fault detection • Compact Panel mount enclosure • Quick installation using side clips (no fixing screws required) • Adjustable Trip level (0.1 – 2A) and Time delay (0.05 – 1s) • LED indication for supply and relay/trip status • Test and Reset buttons • 1 x SPDT Relay output An Earth Fault relay that will monitor and detect when the measured current exceeds the set trip threshold and energises the output relay after the set time delay. The output relay contact comprises a SPDT arrangement. An auxiliary supply (required to power the unit) must be present for the product to function. Specification • Monitoring function: Earth Fault • Tripping characteristic: Definite Time • Trip threshold: 0.1 – 2A • Time delay: 0.05 – 1s • Aux. supply voltage*: 115VAC or 230VAC • Output: SPDT 8A @ 250V (AC1) • Dimensions(mm): W:57 x H:70 x D:84 • Product standard(s): IEC 60255-151

Catalogs