SELL YOUR PRODUCTS
*mydirectindustry  
English

Heat detector 280B-PL series
fireceiling-mountedanalog

heat detector
heat detector
Add to favorites
Compare this product

Characteristics

Detected entity
heat, fire
Other characteristics
ceiling-mounted, analog

Description

The 280B-PL Series heat detectors offer fixed temperature or combination rate-of-rise and fixed temperature features. The heat detector is available with a white plastic reversible mounting plate. The plastic plate can be used for either flush or surface mounting. It includes a white skirt which covers the space between detector base and the mounting surface. *NOTE: Maximum detector coverage has been determined by UL to provide detection time equal to sprinkler devices spaced at 10 ft (3.05m) intervals on a smooth ceiling 15 feet 9 inches (4.8m) high. Higher ceilings may adversely affect detection time. Earlier detection may be obtained by reducing the spacing between detectors. (See NFPA 72, Chapter 5) Detector twists and locks onto mounting plate. Mounting plate may be surface mounted or mounted onto any 3 1/4" (83mm) or 4" (102mm) octagon box. NOTE: Effective July 1, 2015, the 281B-PL and 282B-PL detectors will no longer be manufactured. You may be able to use the 283B-PL or 284B-PL instead if you only need fixed temperature.