Cartridge fuse 10 - 100 A
fast-actingcapacitormedium-voltage

cartridge fuse
cartridge fuse
Add to favorites
Compare this product
 

Characteristics

Configuration
cartridge
Type
fast-acting
Other characteristics
capacitor, medium-voltage

Description

Expulsion fuses (see figure S) are normally used to pro- tect banks with high powers usually installed outside, where there are many units in parallel. Using expulsion fuses is a practical cost-effective and functional system since, in case of failure: - only the unit involved is excluded, keeping the system in service, making it possible to schedule replacement; - searching for the affected unit is easy and fast as it is easy to see thanks to the expulsion device, thereby making it possible to minimize the search time (see figure R); - the fuse can be reused by changing only the internal cartridge element. We should point out that system operation, in the event of failure and ensuing exclusion of one or more units, is only permissible if the increase in voltage on the remai- ning capacitors is less than 10% (minimum number of 10 units in parallel per phase). If use involves a smaller number of units in parallel, the bank of capacitors must be disconnected from the network to avoid damage to the other units that are still integral. It is recommended to use expulsion fuses on banks with a max power of approximately 5 Mvar; this value is based on the need to prevent the current due to the discharge of the energy stored in the units connected in parallel with the defective unit causing the container to break.

Catalogs

No catalogs are available for this product.

See all of Enerlux‘s catalogs
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.