Efficiency improved by approx. 34% compared with previous models*2.
Ideally suited to filling the need to reduce air-conditioning energy costs and improve energy efficiency.
The longer users operate the unit throughout the year, the greater the benefits of conserving the energy in operation that are achieved.
*1 Model EXA (gas-fired (LHV basis), 15-7℃ chilled water temperature condition
Improved efficiency and smaller foot print
Improved efficiency supported by 2-step evaporation and absorption cycle
Higher efficiency has been achieved by the use of a 2-step evaporation and absorption cycle. This cycle is divided into two steps: an upper step and a lower step.
By ensuring that the chilled water has a temperature of 15°C to 11°C and that the cooling water has a temperature of 32°C to 34.5°C for the cycle in the lower step, the concentration of the solution can be reduced to the same level as for low load operation.
As a result, a large difference in the concentration between the generator and absorber can be realized, making it possible to reduce the volume of the circulating solution. In this way, by diminishing the volume of the circulating solution, the amount of heat loss due to the cooling water and the heat generated by the high-temperature generator are reduced and a higher efficiency is successfully achieved for the cycle.