Programmable gas detection control unit GA-ADR.E1
LCD displayaddressablefor DIN rail mounting

programmable gas detection control unit
programmable gas detection control unit
Add to favorites
Compare this product
 

Characteristics

Options
programmable, LCD display, addressable, for DIN rail mounting, S-Bus protocol

Description

Addressable gas controller GA-ADR.E1 manages till 32 gas detectors. GA-ADR.E1 have 3 alarm levels with light and sound indication, 4 relay outputs; RS-485 interface; LCD display, non volatile memory for alarm events; diagnostic of communication lines and gas detectors, the possibility of a external battery power supply. Developed in enclosure for DIN rail mounting. Gas controller GA-ADR.L is compatible with gas sensors GS-ADR.BC.V and GS-300.N. TECHNICAL SPECIFICATIONS: -DIN rail mounting enclosure -input line: RS485 Modbus -output line: RS485 Modbus -alarm levels: 3 -supported gas detectors: GS-ADR.BC.V, GS-300.N -max number of gas detectors: 32 -communication: RS-485 -LCD display -LED indication -relay outputs: 4pcs. (2A/220VAC) -working voltage: mains (230 VAC/50Hz); back up (12 VDC) -non volatile memory for events -sound signalization -real time clock -working temperature: -10 - 50°C -humidity: 30 - 95 % RH -comply with EN 50270, EN 61010
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.