Connection electrical cable CAB-ECS6C1.0
insulatedshieldedATEX

connection electrical cable
connection electrical cable
Add to favorites
Compare this product
 

Characteristics

Protection
insulated, shielded, ATEX
Applications
industrial
Material of the insulation
PVC-sheathed
Other characteristics
connection, insulated
Temperature

Max.: 80 °C
(176 °F)

Min.: -25 °C
(-13 °F)

Cross-section

1 mm²
(0 in²)

Description

CAB-ECS6C1.0 Extension cable suitable for the connection of earthing system from SAFE Area to the junction-box in ATEX Zone USAGE Electric extension cable of the ECS range, for connection from the monitoring System to the junction box. Single section maximum length: 100 m. CONSTRUCTION • - N° 6 conductors with section of: 6x1,00 mm2 • - Conductors insulation: PVC +105°, 0 2,10+0,10 mm. Color: Black • - T otally shielded: 7x0.30, AL/pet tape • - External sheath: PVC 0 8,00+0,30 mm. Color: Blue RAL 5015 CHARACTERISTICS • - Electrical résistance s 19.5 Q/km at 20 °C • - Kilometric inductance at 20 °C s 0.55 mH/km • - Kilometric capacitance at 20 °C s 100 nF/km • - Insulation résistance at 20 °C & 150 MQ/km • - Voltage test: 2.000 V • - Working température -25 °C * T s + 80 °C • - Curvature radius: 10x0