CN-8013 CC-Link Network Adapter
1 Module Overview
CN-8013 CC-Link network adapter supports standard CC-Link Ver.2 communication
and it could monitor the communication status of IO modules in real time
Technical Parameter
Adapter Hardware Parameter
System Power:Nominal :24Vdc,Range: 9-36Vdc
Reverse Protection: YES
Power Consumption:110mA@24Vdc
Internal Bus Supply Current:Max: 2.5A@5Vdc
Isolation:System Power to Field Power Isolation
Power Supply:Nominal:24Vdc, Range:22-28Vdc
Field Power Current:Max. DC 8A
IO Modules Supported:32pcs
Wiring:Max.1.5mm²(AWG 16)
Mounting Type:35mm DIN-Rail
Size:115*51.5*75mm
Weight:130g
Environment Specification
Operation Temperature:-40~85℃
Operation Humidity:5%-95% ( No Condensation)
Protection Class:IP20
CC-Link Parameter
Protocol CC-Link Ver.2
Station Type Remote device station
Number of Logical
Stations Occupied 1, 2, 3, 4
Extended Loop Setup 1 time, 2 times, 4 times, 8 times
I/O Data Capacity RX/RY capacity( bit) max. 896
RWr/RWw capacity( word) max. 128
Baud Rate 156K/625K/2.5M/5M/10Mbps
Node Station (Station No.)
1~64(DIP switch configuration), when DIP switch
value is not 1~64, and the mandatory station number is 1.
Interface 5 Pin screw terminal
Max. bus length 1200m( 156kbps)
Terminal resistance 120ohm