For connection of collective fire detectors (GMT/conventional line, GMT/conventional line with shunt Zener diode barrier (SB3) for explosion-hazard areas). For monitored controls of e.g. smoke dampers, alarm devices, door magnets and extinguishing activation devices (adhere to country-specific instructions). Monitored signal input for status and alarm messages or for acknowledging technical status.
The 2 inputs/outputs can be parameterized autonomously in each case as detector line collective, contact input, control output, control output and input as acknowledgement with selectable monitoring time frame. Status indication by LED.
Transponder incl. 2 Transzorb diode 20 V, 8 resistors and 2 mounting feet for TS35 U-rail.
Operating temperature
-25…60 °C
Standard
CEA GEI I-084 , EN 54-13 , EN 54-17 , EN 54-18
Power supply
External input voltage DC 18...32 V
Protection category
IP30; IP65 with ext. housing
Relative humidity
≤85 % rel.
Operating voltage
FDnet/C-NET DC 12…33 V
EOL resistor
3.3 kΩ/680 Ω, 2.7 kΩ/560 Ω, 3.3 kΩ
Storage temperature
-30...+65 °C
Cable capacity
0.2...1.5 mm2 (2.5 mm2)
Control output
DC 24 V ± 5 % / 2x 1 A or 1x 1.5 A
System compatibility
FDnet -> FS20, AlgoRex, SIGMASYS C-NET -> FS720
Communication protocol
FDnet/C-NET
Detector line
Collective GMT Siemens/Cerberus, Synova conventional/SynoLINE300, collective/SynoLINE600 or similar
Dimensions (W x H x D)
132 x 90 x 24 mm
Color
Pure white, RAL 9010