Dear visitor
1. eYc looking for a partnership for Distributor/Agent/SI
2. For the latest catalogs, please refer to eyc-tech.com
3. The specifications contained herein are subject to change without notice.
For more details, please contact us.
eYc THS07 Temperature & Humidity Transmitter for Probe Type
●Additional option:( ILAC/TAF ) Test report - Standard calibration laboratory ( TAF accreditation:3032, complying with ISO/IEC 17025 )
TAF has mutual recognition arrangement with ILAC MRA
【Features】
● Compact design and easy to install
● An economical choice, high C/P ratio
● Industrial class sensor comes with high accuracy and long-term stability
【Specification】
Input
Signal connection: Capacitive Humidity Sensor & Pt100
Measuring Range: 0 ... 50℃;5 ... 95%RH
Recommended working range: 15 ... 35℃;20 ... 80%RH
Accuracy
Temp.: ±0.3℃ + 0.002℃ x t actual
Humidity (at +25℃): ±3 %RH(30 ... 70%RH) of F.S.
Humidity (at +15 ... 35℃): ±5%RH(20 ... 80%RH) of F.S.
Output
Output : Temp.: RTD ( Pt100 / NTC10K ) / Humidity : 0 ... 10 V ; 4 ... 20 mA
signal connection: 3-wire : Temp. / Humidity : (0 ... 10 V) / 2-wire : Humidity : (4 ... 20 mA) / 4-wire : Temp
Temp. influence: 0.2% RH/℃
Environment
Media measured: Air
Storage temperature: - 5 ... + 60℃
Max. flow speed: ≦ 15 m/sec
【Application】
● Monitoring for HVAC process / Air conditioning / Environmental ventilation control
● Environmental monitoring for building / Factory / Clean / room / Laboratory
● Monitoring for storeroom / Crisper / Agriculture / Food industry
● Temperature and humidity measuring in machinery or equipment