Model: EMJ-110
Form of Construction: Soundproof or Automatic Soundproof
Control panel type AUT-MP12
Diesel engine JOHN DEERE 4045HF158
Alternator LEROY SOMER LSA 442 VS45
Output in standby service on mains failure
(LTP "Limited Time Power" according to norm ISO 8528-1)
110 kVA 88 kW
Output in prime service
(PRP "Prime Power" according to norm ISO 8528-1)
100 kVA 80 kW
Current intensity in standby service on mains failure 159 A
Triphasic voltage 400 V
Voltage precision in steady state ±0,5%
Frequency 50 Hz