Product overviewBESafe is a dual-channel gas detector designed for battery energy storage and similar critical energy environments. It supports simultaneous monitoring of two gases, remote swappable smart sensors, local OLED readout and alarm outputs, enabling fast detection and straightforward field servicing.
Key features- Dual-gas monitoring: two sensors on one transmitter with flexible configuration
- Detection of hydrogen (H2), carbon monoxide (CO), methane (CH4) and other gases via catalytic, electrochemical or infra-red sensors
- Remote, pre-calibrated swappable smart sensors to reduce downtime
- Built-in 128×64 OLED displaying both channels simultaneously
- Audio-visual alarm: sounder 85 dB @ 3 m; LEDs for Power, Fault and Alarm
- Electrical outputs: 2 × 4–20 mA, RS-485 Modbus RTU; SPDT relays for Alarm 1, Alarm 2 and Fault
- Data logging: 3000 data logs
Thermal runaway detection- Provides operators with critical time to respond
- Helps prevent escalation of hazardous events
- Enables fast, reliable safety actions to protect assets and personnel
Monitor hard-to-reach spaces- Flexible installation and remote sensor placement to access confined or obstructed areas
- Compact transmitter form factor simplifies mounting
- Reduces complex cabling by allowing sensors to be located away from the main unit
Reduced downtime and maintenance costs- High-performance pre-calibrated smart sensors with minimal in‑service calibration needs
- Swappable sensor modules for quick field replacement
- Sensor life indicator for proactive maintenance planning
Accessories (examples shown)- Sensor Test Cap C038001
- Gas Tube 1 m (OD 6.4 x ID 3.2) C038002
- Sensor Slot Cover C038004
- Remote Sensor Cable 1 m C038005
- Remote Sensor Cable 2 m C038006
- Remote Sensor Cable 5 m C038007
- Remote Sensor Cable 8 m C038008
- Remote Sensor Cable 10 m C038009
- Remote Sensor Cable 15 m C038010
- M20 Cable Gland C038003
Sensor optionsAny two sensors may be fitted to one transmitter. Catalytic, electrochemical and infra‑red sensor types are supported on the same transmitter.
Gas | Sensor type | Range | Temperature Range | Humidity Range
Hydrogen (H2) | Catalytic | 0–25% LEL, 0–100% LEL | -20 to +60 °C | 0 to 95% RH
Methane (CH4) | Catalytic | 0–25% LEL, 0–100% LEL | -20 to +60 °C | 0 to 95% RH
Carbon Monoxide (CO) | Electrochemical | 0–50 ppm, 0–100 ppm, 0–200 ppm, 0–500 ppm, 0–1000 ppm | -10 to +50 °C | 15 to 90% RH
Hydrogen Sulphide (H2S) | Electrochemical | 0–25 ppm, 0–100 ppm | -30 to +50 °C | 15 to 90% RH
Oxygen (O2) | Electrochemical | 0–25% Vol. | -20 to +50 °C | 15 to 99% RH
Sulphur Dioxide (SO2) | Electrochemical | 0–100 ppm | -30 to +50 °C | 15 to 99% RH
Carbon Dioxide (CO2) | Infra‑red | 0–5000 ppm, 0–5% Vol. | -20 to +50 °C | 0 to 95% RH
Technical specifications- Size: 175 x 150 x 55 mm (transmitter); sensor depth: 33.5 mm
- Weight: Base 550 g; Adapter 169 g; Sensor tray 65 g each
- Enclosure material: Polycarbonate
- Ingress protection: IP65
- Cable entry: M20 knock-out; cable ID 4 mm, OD 6 mm
- Power: 10–30 V DC (24 V DC nominal); 150 mA (3.6 W @ 24 V DC), 5 W max; inrush <1.7 A
- Display: 128×64 OLED, both channels shown simultaneously
- Electrical output: 2 x 4–20 mA; RS‑485 Modbus RTU
- Relays: SPDT for signal circuits, 1 A at 24 V DC (Alarm 1, Alarm 2, Fault)
- Audio-visual output: Sounder 85 dB @ 3 m; LED: Power (Green), Fault (Yellow), Alarm (Red)
- Operating temperature (transmitter): -40 °C to +75 °C (sensor-specific operating ranges apply)
- Operating humidity: 0 to 99% RH (non-condensing); sensor-specific humidity ranges may vary
- Data logging: 3000 data logs
- Approvals: CE, ETL, RoHS; UL 2075 (CO & CH4 sensors), UL 61010-1, EN 61010-1, EN 50270
- Warranty: 2 years on transmitter and sensors