The CDS201 is optimized for demand-controlled ventilation and building automation in residential and commercial applications. This versatile room sensor combines CO₂, temperature (T), and relative humidity (RH) measurement in one device with a modern design and state-of-the-art technology. The elegant enclosure is available in two sizes (EU and US format) and features an optional display.
Outstanding Measurement Performance
The CO₂ measurement of the CDS201 relies on the pollution-resistant E+E dual wavelength NDIR technology. This measuring principle automatically compensates for ageing effects and ensures excellent long-term stability. The multiple point CO₂ and temperature adjustment procedure leads to excellent CO₂ measurement accuracy over the entire temperature working range.
The E+E proprietary sensor coating protects the RH/T sensing element from contamination and corrosive deposits. This improves the measuring performance and service life of the sensing element in dusty or dirty environments.
Outputs and Digital Interface
The CDS201 room sensor features analogue outputs or RS485 interface with Modbus RTU. In the digital version, the CDS201 also calculates the dew point temperature (Td). The measured values can also be read locally on the optional graphic display.
The version with RS485 interface can be set up and configured via PC with the free PCS10 Product Configuration Software and an optional configuration adapter.
Installation-friendly Enclosure
The enclosure of the CDS201 facilitates fast and thus cost-saving installation. The back cover with the push-in spring terminals can be mounted and wired without the front cover. This means that the electronics, which are accommodated in the front cover, are not exposed to construction site pollution. Before commissioning, the active part can be simply snapped onto the back cover. Besides, the electronics part can be replaced without tools within seconds.
Typical Applications
- Demand controlled ventilation
- Heating, ventilation and air conditioning
- Building automation
Key Features
- CO₂, T, RH measurement with a single device
- Calculation of dew point temperature Td (CDS201 with RS485)
- Pollution-resistant CO₂ measuring principle
- RH/T sensing element protected by E+E proprietary coating
- High accuracy due to multiple point CO₂ and T adjustment
- Modbus RTU or analogue outputs
- Large graphic display (optional)
- Snap-on enclosure for time-saving installation
- EU and US enclosure format
- Easy configuration
Technical Data
- Measuring range - CO₂: 0...2,000 ppm / 0...5,000 ppm
- Accuracy - CO₂: 80...100 %RH)
- Measuring range - Temperature: -30...+60 °C (-22...+140 °F)
- Accuracy - Temperature: ±0.35 °C (±0.63 °F), voltage output / RS485; ±0.7 °C (±1.26 °F), current output
- Output analogue: 0-10 V or 4-20 mA
- Output digital: RS485 (Modbus RTU)
- Power supply: 15-35 V DC or 24 V AC ±20 %
Additional Features
- High CO₂ / RH / T accuracy
- Excellent long-term stability
- State-of-the-art E+E sensing elements (CO₂: NDIR dual wavelength; RH / T: protected by E+E proprietary coating)
- Innovative design avoids false air ingress
- Time-saving installation and wiring (snap-on without tools, push-in spring terminals, all electronics inside the front cover)
- Smooth cover surface (dust repellent, easy cleaning)
- UL94HB approved enclosure material
- Three analogue outputs (0 - 10 V, 4 - 20 mA)
- RS485 interface with Modbus RTU and BACnet MS/TP
- Large graphic display
- Inspection certificate available via certificates.epluse.com