OverviewSocket and small-type distributors designed for temporary power distribution on construction sites and similar installations. Available in rubber or plastic housings and multiple model variants (SV, SVK) offering different connection ratings, input fuses and socket combinations to match site requirements.
Types and technical data (overview)Type | Ref. No. | kVA | Connection fuse | RCD Typ A | RCD Typ B (all-current sensitive) | Earth-contact sockets | CEE 16A | CEE 32A | CEE 63A
SV 16S/6 | 189750 | 3,6 | SKSD 16A | 1x25/0,03A | - | 6 | - | - | -
SV 16/6 | 189751 | 11 | CEE 16A | 1x25/0,03A | - | 6 | - | - | -
SV 32/6 | 189754 | 22 | CEE 32A | 1x40/0,03A | - | 6 | - | - | -
SV 16N/A/41 | 183300 | 11 | CEE 16A | - | 1x40/0,03A | 4 | 1 | - | -
SV 16N/A/32 | 183301 | 11 | CEE 16A | - | 1x40/0,03A | 3 | 2 | - | -
SV 32N/A/311 | 183302 | 22 | CEE 32A | - | 1x40/0,03A | 3 | 1 | 1 | -
SV 32N/A/312 | 183303 | 22 | CEE 32A | - | 1x40/0,03A | 3 | 1 | 2 | -
SV 32N/A/321 | 183304 | 22 | CEE 32A | - | 1x40/0,03A | 3 | 2 | 1 | -
Rubber-housing distributors without RCDNote: These distributors are intended to be used with an upstream construction-site distributor equipped with an RCD. Residual-current protection must be ensured by the upstream unit.
Type | Ref. No. | kVA | Connection fuse | RCD Typ A | RCD Typ B | Earth-contact sockets | CEE 16A | CEE 32A
SV 16S/O/8 | 183310 | 3,6 | SKSD 16A | - | - | 8 | - | -
SV 16/O/8 | 183311 | 11 | CEE 16A | - | - | 8 | - | -
SV 16/O/62 | 183312 | 11 | CEE 16A | - | - | 6 | 2 | -
SV 32/O/611 | 183313 | 22 | CEE 32A | - | - | 6 | 1 | 1
Plastic-housing distributorsType | Ref. No. | kVA | Connection fuse | RCD Typ A | RCD Typ B | Earth-contact sockets | CEE 16A | CEE 32A | CEE 63A
SVK 32N/A/621 | 183305 | 22 | CEE 32A | - | 1x40/0,03A | 6 | 2 | 1 | -
SVK 63N/A/622-G | 183306 | 44 | CEE 63A | - | 1x63/0,03A | 6 | 2 | 2 | -
SVK 63N/A/821-G | 183307 | 44 | CEE 63A | - | 1x63/0,03A | 8 | 2 | 1 | -
SVK 63N/A/6111-G | 183308 | 44 | CEE 63A | - | 1x63/0,03A | 6 | 1 | 1 | 1
Additional notesModels are offered with different RCD configurations (Type A and all-current-sensitive Type B) or without an integrated RCD for use with an upstream RCD-protected feed. Connection types include SKSD 16A, CEE 16A, CEE 32A and CEE 63A. Socket counts and CEE socket combinations vary by model.
Characteristics / technical specifications- Housings: rubber or plastic options depending on model.
- Typical connection ratings (kVA): 3.6, 11, 22, 44.
- Input connections: SKSD 16A, CEE 16A, CEE 32A, CEE 63A depending on type.
- RCD options: Type A, all-current-sensitive Type B, or no integrated RCD (upstream protection required).
- Varied counts of earth-contact sockets (2P+E/230 V) and combinations of CEE outlets to suit site equipment.
- Product datasheets available for each type (refer to catalogue reference numbers).