2x4 digits LCD display
Double set point
Selectable sensor type (Pt-100, J, K, L, T, S, R)
PID control function with accurate self-tuning
Digital inputs can be assigned to 3 different feature
Function key can be assigned to 3 different feature
Soft-Start function
Selectable SSR or relay control output
Alarm2 or temperature control output can be programmed as C/A2 relay output
Alarm1 output or PID cooling output can be programmed
Selectable heating and cooling control
Offset feature for input
In the case of probe failure periodical running or relay state can be selected
Communication via RS-485 ModBus protocol
CE marked according to European Norms
Environmental Conditions
Ambient/Storage Temperature - 0...50 ºC / -25...70 ºC
Relative Humidity - 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Protection Degree - According to EN 60529 Front panel: IP65, Rear panel: IP20
Height - Max. 2000m
Electrical Characteristics
Supply - 90-250V AC +10% - 20%, 50/60Hz, 24V AC ±10%, 50/60Hz or 10-30V DC / 8-24V AC ±10% SMPS
Power Consumption - 5VA
External Connections - Plug-in terminals
Scale - Pt-100 resistance thermometer -199.9...600.0 °C / -200...600 °C
Fe-Const (J) thermocouple -30...600 °C / -30.0...600.0 °C
NiCr-Ni (K) thermocouple -30...1300 °C / -30.0...-999.9 °C
Fe-CuNi (L) thermocouple -30...600 °C / -30.0...-600.0 °C
Cu-CuNi (T) thermocouple -30...400 °C / -30.0...-400.0 °C
Pt10Rh-Pt (S) thermocouple -40...1700 °C
Pt13Rh-Pt(R) thermocouple -40...1700 °C
Accuracy - ±0.5% (of full scale) ±1 digit thermocouple), ±0.2% (of full scale) ±1 digit (Pt-100 resistance thermometer)
Line Resistance - Max. 100ohm
Output