FESTEC’s IEC 60331-11 tester is used in test conditions where the basic flame temperature is at least 750℃ and tests the cable exposed to the flame that needs to maintain the circuit integrity.
• IEC 60331
- Test for electric cables under fir conditions – Circuit integrity
• IEC 60331 Part 11
- Apparatus – Fire alone at a flame temperature of at least 750˚C
• IEC 60331 Part 21
- Procedures and requirements – Cables of rated voltage up to and including 0.6/1kV
• KWS 409 : Wire of Fire Resistance (Fire-Resistence) - 5.14 Fire resistance test
Specification
- Test Chamber Size : (W) 1,600 x (D) 500 x (H) 500
- Heat Source : Ribbon type Propane Gas Burner
- Burner Dimension : (L) 500 x (W) 10 mm / Space of hole : 3.2mm
- Flame Failure device, Control thermocouples
- Pilot feed, Gas flow, Rotameter-type flowmeters
- Auto Ignition system
- Mass Flow Controller
; Gas : 15 SLPM / Signal Output : 0 ~ 5V / Accuracy : ±1 % fo F.S
; Air : 180 SLPM / Signal Output : 0 ~ 5V / Accuracy : ±1 % fo F.S
- Electric Control : Transformer & Slidacs : 3 Phase 3 wire, 100~1,000V
- DAQ System
; 16 channel Analog Input / Output, 200ks/s
; 16 channel Digital Input / Output
- Control Rack : (W) 730 x (D) 650 x (H) 1,400 / 19” Rack / Each Assembly Connector