The Universal X1-IS-UNI-01 module is a high integrity interface suitable for applications requiring SIL 3 or SIL 2 level (depending on applications) in safety related systems for high risk industries. Thanks to its high flexibility, it can interface 2-wire active/passive 4-20 mA (AI), smart positioners (AO), switches and proximity detectors (DI), as well as solenoid valves and other process control devices (DO) located in Hazardous Area. HART® communication is supported for both active and passive transmitters, and I/P. The module always sinks current and the Termination Board extends its use to source loops. Programmable line and load open/short circuit detection and out-of-range current fault is also provided. The module automatically matches the application, without reprogramming; if required, it can be re-calibrated through the configuration software. To ease maintenance operations, field devices can be disconnected through a two-position insertion/extraction mechanism. This product requires a dedicated Termination Board.
- SIL 3/2 depending on applications / SC 3
- Input from Zone 0 / Division 1
- Installation in Zone 2 / Division 2
- Loop disconnection to ease maintenance operations
- Suitable for AI, AO, DI and DO applications without configuration
- HART® compatible (passive and active AI/AO loops)
- Line & Load short/open circuit programmable diagnostics
- Out-of-range fault with programmable thresholds
- Digital calibration available through configuration software
- Input and Output short circuit proof
- Field fault mirroring to the DCS/PLC UNI Card
- High Accuracy
- Three port isolation, Input/Output/Supply
Technical Specifications:
- AI Power dissipation: 0.90 W (pass. Tx), 1.05 W (act. Tx) with 20 mA, 24 V + 250 Ω @ 24 Vdc, typical.
- AO Power dissipation: 0.75 W with 20 mA on I/P out @ 24 Vdc, typical.
- DI Power dissipation: 0.95 W with short circuit input @ 24 Vdc, typical.
- DO Power dissipation: 1.60 W with 40 mA, 1.40 with 35 mA @ 24 Vdc, typical.
- System Supply Voltage: 24 Vdc nom (18 to 30 Vdc).
- AI Current consumption: 32 mA (passive Tx), 18 mA (active Tx) with 20 mA @ 24 Vdc, typical.
- AO Current consumption: 30 mA with 20 mA on I/P out @ 24 Vdc, typical.
- DI Current consumption: 30 mA with short circuit input @ 24 Vdc, typical.
- DO Current consumption: 67 mA with 40 mA @ 24 Vdc, typical.
- System In/Out Type: Current 0 to 40 mA, mirrored from Field. The module always sinks current and the Termination Board extends its use to source loops.
- Response time: 5 ms.
- Maximum load: 600 Ω (AI usage).
- Minimum voltage: 15 V (AI, DI, DO usage).
- Maximum voltage: 30 V (all applications).
- Field In/Out Type: Field interface specs depend on terminals and usage.
- Current limitation: 45 mA, typical, for all applications.
- AI: Current 4 to 20 mA, passive or active Tx + HART.
- AI Passive Tx line voltage: 15.5 V minimum @ 20 mA.
- AI Active Tx voltage drop: 6.5 V maximum @ 20 mA.
- AO: Current 4 to 20 mA + HART.
- AO Maximum load: 600 Ω.
- DI: 8 V/1 kΩ typical, according to NAMUR standard.
- DO: 0 to 40 mA, linear derating from 40 mA (60 °C) to 35 mA at (70 °C).
- DO Output voltage: 8.5 V minimum @ 40 mA.
- Fault Type: Load short/open with settable limits on voltage, current and resistance.
- Fault signalling: common fault & fault mirroring on DCS/PLC IO.
- Performance Reference Conditions: 24 V supply, 250 Ω load, 23 ± 1 °C Tamb.
- Calibration accuracy: ≤ ± 20 µA.
- Linearity accuracy: ≤ ± 20 µA (4 to 20 mA), ± 60 µA (0 to 40 mA).
- Temperature influence: ≤ ± 2 µA/°C.
- Isolation: Field InOut/System InOut 2.5 kV; Field InOut/System Supply 2.5 kV; System InOut/System Supply 500 V.
- Operating temperature: –40 to +70 °C
- Storage temperature: –45 to +80 °C.
- Equipment: Associated apparatus and non-sparking electrical equipment.
- Safety parameters: Uo = 26.7 V, Io = 92 mA, Po = 610 mW at terminals A-Z. Uo = 10.7 V, Io = 11 mA, Po = 29 mW at terminals C-Z. Uo = 1.1 V, Io = 56 mA, Po = 16 mW at terminals B-Z. Ui = 30 V, Ii = 120 mA, Ci = 0.6 nF, Li = 0 µH at terminals B-Z. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.
- Mounting: On custom Termination Board.
- Weight: about 50 g.
- Dimensions: Width 10 mm, Depth 80 mm, Height 120 mm.