video corpo

Differential pressure transmitter PS 27
4-20 mA0-10 V0-5 V

Differential pressure transmitter - PS 27 - halstrup-walcher GmbH - 4-20 mA / 0-10 V / 0-5 V
Differential pressure transmitter - PS 27 - halstrup-walcher GmbH - 4-20 mA / 0-10 V / 0-5 V
Differential pressure transmitter - PS 27 - halstrup-walcher GmbH - 4-20 mA / 0-10 V / 0-5 V - image - 2
Differential pressure transmitter - PS 27 - halstrup-walcher GmbH - 4-20 mA / 0-10 V / 0-5 V - image - 3
Differential pressure transmitter - PS 27 - halstrup-walcher GmbH - 4-20 mA / 0-10 V / 0-5 V - image - 4
Differential pressure transmitter - PS 27 - halstrup-walcher GmbH - 4-20 mA / 0-10 V / 0-5 V - image - 5
Differential pressure transmitter - PS 27 - halstrup-walcher GmbH - 4-20 mA / 0-10 V / 0-5 V - image - 6
Add to favorites
Compare this product

Characteristics

Pressure type
differential
Output
4-20 mA, 0-10 V, 0-5 V, 2-wire
Electrical connection
M12 connector, M16 conector
Supply voltage
24VDC, 32VDC, 15VDC, 24VAC
Mounting
panel-mount, DIN rail, surface-mount
Fluid
for gas
Protection level
IP65
Applications
for HVAC systems
Other characteristics
compact, two-wire, with digital display
Pressure range

Max.: 10,000 Pa
(1.45 psi)

Min.: 50 Pa
(0.01 psi)

Precision

2 %, 3 %

Process temperature

Max.: 60 °C
(140 °F)

Min.: -20 °C
(-4 °F)

Description

Compact differential pressure transmitter for positive or negative differential pressures in basic applications Special features • ± measurement ranges and asymmetric measurement ranges • Either with 1 fixed measurement range or toggling between 4 different measurement ranges (can be selected via DIP switches, optional) • Suitable for top-hat rail mountingand wall surface installation • Selectable output signal 0/2 .. 10 V, 0/4 .. 20 mA or 0 .. 5 V • Can be calibrated • Zero-point calibration via an external signal reduces maintenance costs • The adjustable limit switch permits the connection of, e.g. ventilators or signalling devices, and saves additional wiring (optional) • Electrical connection: With standard M16 cable gland, optional 4-pin M12 plug with A-coding This compact differential pressure transmitter is particularly suited to filter and pressure monitoring applications in the heating, air-conditioning and ventilation industries. Options The instrument is available with an factory calibration certificate or calibration certificate according to DKD-R 6-1. An optional display allows measurement values to be read directly on-site in Pa or kPa. An optional time constant (up to 4s) allows the instrument to generate an attenuated output signal, even under fluctuating pressure conditions. To reduce wiring costs, the instrument is also available in a version with two-wire technology (optional). Pressure ports also as push-in fittings on request
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.