Ultrasonic level sensor AS-ULM
for solidsfor liquidsRS-485

Ultrasonic level sensor - AS-ULM - Hurricane PZT - for solids / for liquids / RS-485
Ultrasonic level sensor - AS-ULM - Hurricane PZT - for solids / for liquids / RS-485
Add to favorites
Compare this product

Characteristics

Technology
ultrasonic
Medium
for liquids, for solids
Interface
RS-485
Other characteristics
high-precision, submersible, flexible, with LED indicator, non-intrusive, with remote electronics
Level range

Min.: 0.03 m
(0'01" )

Max.: 60 m
(196'10" )

Description

Product Overview
Ultrasonic Level Meter AS-ULM is a split-design, non-contact sensor for continuous level measurement of liquids and solids. The transducer is rated IP68 for submerged use while the separated transmitter is accessible for installation and maintenance. Typical output is RS485 (default) with accuracy between 0.5% and 1.0% and a measurement range from 30 to 60,000 mm.

Key Features
  • Measurement range: 30–60,000 mm
  • Split transducer and transmitter design for flexible mounting
  • Non-contact ultrasonic measurement suitable for liquids and solids
  • Output interface: RS485 (default)
  • Accuracy: 0.5–1.0%
  • Transducer protection: IP68; transmitter protection: IP61
  • Power supply: 10–28 VDC (default)
  • LED display resolution: ≥ 1.5 mm

Specifications Summary
  • Model: AS-ULM
  • Measurement principle: Non-contact ultrasonic
  • Measurement range: 30–60,000 mm
  • Output interface: RS485 (default)
  • Accuracy: 0.5–1.0%
  • Power supply: 10–28 VDC (default)
  • Transducer protection: IP68
  • Transmitter protection: IP61
  • LED display resolution: ≥ 1.5 mm
  • Suitable media: Liquids, solids

Applications
  • Liquid level measurement in storage and process tanks
  • Water and sewage monitoring
  • Solid distance and level measurement in hoppers and bins
  • Telemetry and SCADA system input

Installation & Maintenance
  • Mount the transducer on the tank roof or a rigid bracket with a clear acoustic path to the measured surface
  • Use the split transmitter for convenient access and longer cable runs between sensor and electronics
  • Integrate via RS485 for remote monitoring and parameter configuration
  • Inspect and clean the transducer periodically in applications with heavy solids, foam or buildup