1. Application
HYDRA PRB DPM(g) three-phase capacitors are designed
for power factor correction (PFC) in low voltage networks.
They may be used for:
- individual fixed PFC of motors, transformers, etc.
- automatic PFC equipment
- tuned and detuned capacitor banks
2. Construction
The HYDRA PRB DPM(g) capacitors have three separate
windings from metalized polypropylene film placed in a
cylindrical aluminum can. The partial capacitances may be
connected either in star or delta configuration. The use of
three separate stacked windings guarantees low losses,
optimal surge current performance and good heat drain from
the windings. A high-vacuum drying of the windings gives long
service life with constant capacitance.
HYDRA capacitors are filled with a PCB-free natural oil
(PRB DPM) or with gas (PRB DPMg).
3. Terminals
The terminal is designed as a double 3-pole terminal block
(IP20). It is possible to clamp multiple-wires with a cross
section up to 35 mm²
4. Self-healing
Due to switching operations, inadmissible voltage peaks of up
to 3 times that of the rated voltage can occur in low voltage
networks. If these stresses affect a dielectric breakdown, the
self-healing mechanism will function. After self-healing, the
capacitor continues its complete operation. The decrease in
capacitance is negligible.