Description- This sensor measures the differential pressure between two work areas to limit contamination risks in cleanrooms. It ensures precise airflow control to maintain optimal and safe conditions.
- Differential pressure transmitter ΔP for monitoring differential pressure.
- Sensors matched to each pressure range for accurate measurement.
- Designed for differential pressure monitoring in cleanrooms.
- Compatible with Nano SPY U or LoRa SPY U recorders.
Specifications tableMeasurement range: 30/50/100 Pa
Operating conditions: 0 to 70°C
Response time: < 20 ms
Accuracy: ±1% FS
Mounting: Wall (enclosure)
Supply: 8-33 VDC
Output: 4-20 mA
Weight: 90 g
Protection: IP54
Compliance: CE per EN 61326-2-3
Technical characteristics / specifications- Measurement range: 30/50/100 Pa
- Operating conditions: 0 to 70°C
- Response time: < 20 ms
- Accuracy: ±1% FS
- Mounting: Wall (enclosure)
- Supply: 8-33 VDC
- Output: 4-20 mA
- Weight: 90 g
- Protection rating: IP54
- Compliance: CE per EN 61326-2-3