Operated with 230 V mains voltage and is therefore without ballast unit
Potential-free contact for message "Not CLOSED" (contact closes when leaving position CLOSED)
Technical data
Electrical properties
Rated voltage
230 V AC/50 Hz (-15 %/+10 %)
Nominal current
approx. 0.2 A
Cut-off
electronic load cut-off, built-in
Class of protection
II
Mechanical properties
Stroke length aprox.
82, 300, 500 and 750 mm
Pressure force
max. 500 N
Tractive force
max. 250 N
Locking force
2000 N
Running speed
approx. 10 mm/s
Duty cycle
ED 30 (10 min)
Service life
> 10.000 cycles
Dimension (L x W x H)
(stroke + approx. 133 mm) x 82.5 x 41 mm;
Minimum istallation length 433 mm
Electrical connection
Connection
5 x 0.75 mm², legth approx. 1.60 m, grey
Installation and ambient conditions
Ambient temperature range
–5 °C up to +75 °C
Protection category
IP 44
Depending on the control panels used, increased currents in the starting torque must be taken into account when dimensioning the power supply and the cable cross-sections of the motor supply lines. Reliable operation is guaranteed when connected to appropriate control units from the same manufacturer. For operation on control systems from other manufacturers, conformity for functional safety must be requested.
The drives are equipped with an integrated switching power supply for operation on 230 V AC mains voltage. Suitable switching and relay contacts must therefore be used to control the drives.