• For SHE and ventilation
• Up to 4 drives can be synchronized
• Synchronization and reference run can be carried out without EasyDrive software
• Stroke, speed, force: separately adjustable for OPEN/CLOSE via EasyDrive software
• Integrated signaling contact, function configurable
• Two connection terminals for simple connection between the drives
• Adjustable sealing relief
Technical data
Electrical properties
Rated voltage
24 V DC (-10 %/+25 %)
Permissible ripple voltage
2 Vss
Nominal current
0.8 A
Cut-off
integrated, electronic load cut-off
Class of protection
III
Mechanical properties
Stroke length aprox.
EM/EasyDrive/511: 21-511 mm
EM/EasyDrive/603: 21-603 mm
EM/EasyDrive/810: 21-810 mm
Pressure force
max. 300 N
Tractive force
300 N
Locking force
3000 N
Running speed
4-10 mm/s
Duty cycle
ED 30 (10 min)
Service life
> 10.000 cycles
Dimension (L x W x H)
EM/EasyDrive/511: 820 x 40 x 40 mm
EM/EasyDrive/603-810: 1011 x 40 x 40 mm
Electrical connection
Connection
6-pin, connection cable not included in the scope of delivery
Installation and ambient conditions
Ambient temperature range
–10 °C up to +60 °C
Protection category
IP 20