OverviewMersen's Critical Power Panel (CPP) series is a UL 67 panelboard designed for critical electrical loads, offering a reduced footprint and weight to speed installation and lower installed cost. The CPP supports fused mains and branch protection with Mersen Compact Fused Disconnect (CEP) and Amp-Trap 2000® fuses.
Key benefits- Minimized connection points to reduce electrical and mechanical failure locations
- Steel back plate for component mounting
- High interrupting rating: 200 kA with upstream protection (25 kA standalone)
- Easy selective coordination using Mersen Amp-Trap 2000® fuses and CEP disconnects
Product detailsThe CPP is available with switched fused mains up to 400 A, using Mersen UL 98 rated Compact Fused Disconnect (CEP) and Amp-Trap 2000® Class CC or Class J fuses for branch protection. Fuse types can be selected to provide application-specific time delay or faster clearing. The panelboard, main and branch circuits are rated for use up to 600 VAC or 125 VDC.
Typical applications- UPS systems
- Data centers
- Medium-voltage eHouses
- Emergency circuits (NEC 700.27)
- Legally required standby systems (NEC 701.18)
- Lighting and other loads up to 30 A (Class CC)
- Larger loads (motors, transformers) up to 60 A (Class J)
Other features and options- Integral surge protection (recommended on critical circuits)
- Feed-through lugs
- Standard dual/sub feed lugs on MLO mains
Selective coordinationSelective coordination is typically verified by a short-circuit coordination study. Coordination with the CPP is achieved using upstream Mersen fuses. The CPP utilizes the CEP Compact Fused Disconnect and Amp-Trap 2000® (ATDR, AJT or equivalent) Class CC or Class J fuses for branch protection. Maintain approximately a 2:1 ratio with upstream Amp-Trap 2000® fuses to achieve coordination where applicable.
Relevant NEC sections for critical circuits- 620.62 – Elevator circuits
- 700.27 – Emergency systems
- 701.18 – Legally required standby systems
SpecificationsMechanical CharacteristicsHeader options: Class CC or Class J
cULus certification: UL 67 & CSA 22.2
IEC certification: IEC 60529 IP20
Touch-safe design: No exposure to energized components during normal operation
Electrical CharacteristicsHeader options: Class CC or Class J
System ampacity: 250 A or 400 A
Branch circuit ampacity: Class CC = 30 A; Class J = 30 A and 60 A
Voltage rating: 600 VAC & 125 VDC
Voltage type: Delta or Wye; 1φ or 3φ; 2, 3 or 4 wire
Withstand (SCCR): 200 kA with upstream protection (25 kA standalone)
Neutral sizing: 100 A/200 A/250 A models = 200% neutral; 400 A models = 125% neutral
ConfigurationsHeader options: Class CC or Class J
Enclosure: UL 50 Type 1 (indoor)
Interior only: Available as single unit
Main Incoming (examples)MLO: (1) #2 to 750 kcmil
(2) 1/0 to 350 kcmil
100 A MFS: #2 to 2/0
200 A MFS: #6 to 300 kcmil
400 A MFS: #2 to 600 kcmil
Cable lugs and parallel cablesSingle cable (compression lug): (2) #4–4/0 compression lug
Single cable (crimp lug): #4–4/0 crimp lug
Parallel cables (compression lug): #8–1/0 compression lug
Parallel cables (crimp lug): #8–1/0 crimp lug
Circuitry & CircuitsCircuits (Class CC): 24, 36, 42
Circuits (Class J): 30 A J series: 24 CKT, 36 CKT, 42 CKT; 60 A J series: 6 CKT, 12 CKT, 24 CKT; Hybrid 30 A/60 A J series: 24 CKT/6 CKT, 24 CKT/12 CKT
CompatibilityFor use with Mersen Model CEP — Compact Fused Disconnect (Class CC and Class J compatible)
Technical specifications- Certifications: cULus (UL 67 & CSA 22.2), IEC 60529 IP20
- System ampacity: 250 A or 400 A
- Branch ampacity: Class CC = 30 A; Class J = 30 A and 60 A
- Voltage rating: 600 VAC & 125 VDC
- Voltage type: Delta or Wye, 1φ or 3φ, 2/3/4 wire
- SCCR: 200 kA with upstream protection (25 kA standalone)
- Neutral sizing: 100 A/200 A/250 A models = 200% neutral; 400 A models = 125% neutral
- Enclosure: UL 50 Type 1
- Branch configurations: Double column options
- Compatibility: Designed for use with Mersen CEP Compact Fused Disconnect and Amp-Trap 2000® fuses