OverviewA generator fuel tank stores diesel or light fuel oil to keep standby generators running during power outages. Common configurations include sub-base (belly) tanks that mount under the genset, generator day tanks that feed the engine, and bulk tanks for centralised fuel supply.
Product Types- Sub-base / belly tanks (integral generator base tank)
- Generator day tanks (engine-mounted supply)
- Bulk diesel storage tanks
- Fuel-polishing and transfer-ready units
Design & DeliveryTanks are built to order and sized to the generator rating and required autonomy. Available as single-wall or double-wall (self-bunded) units for indoor plant rooms or outdoor sites. Delivered with required fittings, mechanical contents gauge, level transmitters and alarms for direct connection to generator fuel systems.
Key Features & Advantages- Double-wall (self-bunded) option — eliminates need for separate civil bund
- Interstitial leak detection on double-wall tanks for early warning
- Steel construction compliant with EN 12285-2 / UL-142
- Level transmitters with high-high and low-low alarms
- BMS-ready volt-free contacts and Modbus signalling
- Sized precisely to generator kVA and required autonomy
- Full-drainage, easy-clean tank design for maintenance
- Corrosion-protected steel with ISO 12944 (C4 / C5-M) coating options
- Supplied with gauges, alarms and fittings ready to connect
- Suitable for indoor plant rooms or outdoor installations
- Lower installed cost compared with a concrete bund for self-bunded designs
Capacities & ConfigurationsStandard generator day tanks typically range from 200 to 5,000 litres; base and bulk tanks are manufactured to any project-required capacity. Net volume is calculated from fuel consumption (L/h) × required autonomy (h) with margins for expansion and fill setpoints.
Available Tank Configurations- Single-wall or Double-wall (self-bunded)
- Indoor or Outdoor installation
- Horizontal, Vertical or Sub-base (belly)
Construction, Coating & TestingFabricated from certified structural steel plate with fully welded, pressure-tested seams. Wall thickness selected for capacity and installation. Internal and external surfaces shot-blasted and coated to ISO 12944 (C4 or C5-M) matched to exposure. Each tank is pressure- and leak-tested before dispatch and fitted with labelling and warning signs as requested.
Instrumentation & Leak DetectionSupplied with level instrumentation including level transmitter and high-high / low-low switches for overfill and pre-alarm; mechanical contents gauge for local reading; interstitial monitoring on double-wall tanks to detect primary containment breaches before fuel escape.
ApplicationsNeftgen generator fuel tanks are engineered for mission-critical standby power where fuel-supply reliability is essential: data centres, hospitals, airports, ports, telecom sites and industrial plants. Tanks are sized for commercial building runtimes and extended autonomies (typically up to 24–96 hours for high-availability data centres).
Accessories & EquipmentTypical accessories include transfer sets, fuel-polishing systems, level instrumentation, gauges, alarms and leak-detection systems integrated with control and BMS signalling.
Technical specifications- Construction materials: certified structural steel plate, fully welded seams, pressure-tested
- Coating: shot-blasted and coated to ISO 12944 (C4 / C5-M) for indoor/outdoor use
- Standards: EN 12285-2, UL-142; designed to relevant NFPA standards where applicable
- Manufacturing quality: ISO 9001
- Containment: single-wall or double-wall (self-bunded) with monitored interstitial space
- Leak detection: continuous interstitial monitoring on double-wall tanks
- Level instrumentation: level transmitter plus high-high and low-low level switches; mechanical contents gauge
- Alarms & Signals: high-high, low-low alarms; volt-free contacts; Modbus outputs (BMS-ready)
- Capacities: day tanks 200–5,000 L standard; base/bulk tanks to project requirements
- Fuel types: diesel, gas oil, MGO, light fuel oil
- Installation types: indoor plant-room or outdoor site; horizontal, vertical or sub-base
- Design sizing: net volume = fuel consumption (L/h) × required autonomy (h) + expansion/fill margin
- Testing: pressure- and leak-tested prior to dispatch
- Drainage & maintenance: full drainage and easy-clean design
- Optional features: enhanced corrosion protection, customised painting/marking and bespoke structural designs as required