GeneralThe GZDW series direct-current power supply cabinet is a cabinet-type DC power system for industrial and utility applications. It provides stable DC outputs for control, signalling, communication, protection, emergency DC lighting and DC motor starting, and is suitable for power stations, substations, telecommunications and similar facilities.
Product overviewThe cabinet integrates either high-frequency switching power modules or phase-controlled rectifier (thyristor) charging devices for float and maintenance charging. The system manages battery charging stages (main, equalization, float) and monitors battery condition to extend service life. Models equipped with PLC or microcontroller controllers support remote control and status monitoring to increase system automation and reliability.
Service conditions- Installation: indoor (can be installed in box-type substations)
- Ambient temperature: -10°C to +40°C, daily average ≤35°C
- Altitude: ≤2000 m
- Relative humidity: daily average ≤95%, monthly average ≤90% (at 20°C)
- Mounting: vertical, tilt ≤5°
- Pollution level ≤3; no conductive dust, explosive media or corrosive gases; good airflow required
- Seismic intensity < 8; site free from strong vibration and impact
- No strong electromagnetic interference; external magnetic induction ≤0.5 mT
- AC input: sinusoidal, non-sinusoidal content ≤10%; three-phase imbalance ≤5%
Working principle and controlPLC or microcontroller units perform centralized monitoring and control of the DC panel: manage charge/discharge of batteries, battery inspection, bus voltage regulation, alarm and data logging. Typical communication: RS485 interface with Modbus protocol for remote monitoring and integration into SCADA or asset management systems.
Charging modes- Main charging: device supplies constant current until set average charging voltage is reached, then switches to constant-voltage charging for battery activation and initial charge
- Equalization charging: when charging voltage reaches equalization level the device maintains constant-voltage charging with current limiting; after equalization time it switches to float
- Float charging: constant-voltage maintenance to compensate self-discharge and supply DC loads and control circuits
Technical parameters- AC input: AC380V ±15% (standard) 50Hz ±5%; optional AC220V ±10% (wall-mounted)
- DC output voltages: DC220V, DC110V, DC48V
- Output current ranges: control bus (KM) 5–200A; closing bus (HM) 5–3000A
- Battery capacity supported: sealed lead-acid maintenance-free 10Ah–3000Ah
- Panel dimensions: 2260 × 800 × 600 mm or 2360 × 800 × 600 mm (customizable)
Charging device technical parametersKVAD5 thyristor fully-controlled floating charger / High-frequency switching charger
Voltage stabilization accuracy: ≤ ±1% / ≤ ±0.5%
Current stabilization accuracy: ≤ ±1% / ≤ ±0.5%
Ripple factor: ≤ 1% / ≤ 0.1%
Efficiency: > 85% / > 90%
Noise: < 55 dB / < 55 dB
Characteristics / specifications- Series: GZDW
- Charge modes: constant-current, constant-voltage, equalization, float
- Intelligent battery management and optional PLC/microcontroller automation
- Monitoring/communication: RS485/Modbus typical
- Charging device options: KVAD5 thyristor or high-frequency switching power supply
- Customizable cabinet sizes and battery capacity ranges according to user requirements