Over-frequency protection relay PCS-902
distanceover-voltageunder-voltage

Over-frequency protection relay - PCS-902 - NR Electric - distance / over-voltage / under-voltage
Over-frequency protection relay - PCS-902 - NR Electric - distance / over-voltage / under-voltage
Add to favorites
Compare this product

Characteristics

Measured/monitored value
over-frequency, distance, over-voltage, under-voltage, thermal, under-frequency, phase, earth-leakage, phase sequence
Applications
transmission line
Communication
RS485, USB, Ethernet, Modbus
Norms
IEC
Other characteristics
multifunction, with fault indication, programmable, digital, configurable

Description

Overview
The PCS-902 is a line distance protection relay designed for overhead and underground transmission lines. It provides high-speed sub-cycle distance elements (DPFC) and advanced power swing blocking to ensure selective and reliable fault clearance. Applicable to series-compensated, double-circuit, heavily loaded, weak-in-feed, short and long lines. Supports single-pole and three-pole tripping, single- and three-pole auto-reclosing, single- or dual-breaker schemes and optional dual CT inputs.

Protection and Control
  • Five-zone phase-to-phase distance protection (21P) and five-zone phase-to-ground distance protection (21G)
  • Pilot scheme zones for phase and ground (85)
  • High-speed DPFC distance protection (21D)
  • Pilot directional earth-fault protection (85)
  • Phase, neutral and negative-sequence overcurrent stages (50/51P, 50/51G, 50/51Q)
  • Breaker failure protection for one or two breakers (50BF)
  • Stub overcurrent protection (87STB) and broken conductor protection (46BC)
  • Switch-onto-fault (SOTF) logic and unique power swing blocking/releasing logic (PSBR)
  • Out-of-step protection (78), dead zone protection (50DZ) and thermal overload (49)
  • Pole discrepancy protection (62PD), reverse power (32R) and undervoltage/overvoltage and frequency protections (27/59, 81)
  • Single and/or three-pole auto-reclosing, dual-breaker auto-reclosing and dual synchro-checks (79, synchronism check 25)
  • Remote/local control of circuit breaker, disconnector and earthing switch


Monitoring and Measurement
  • Energy measurement (active/reactive, import/export)
  • CT and VT failure supervision
  • Fault phase selection and Fault Locator with parallel-line compensation
  • Event recorder (change-of-binary, supervision, control and device logs) and disturbance recorder with COMTRADE-compatible waveforms
  • Pilot channel supervision, system frequency supervision
  • Clock synchronization: IRIG-B, SNTP, PPS, PPM and IEEE 1588
  • Self-diagnostic functions


Communication
  • Optional single- or dual-pilot channels (fiber) compatible with G.703 and C37.94
  • Up to four 10Base-T/100Base-TX copper Ethernet ports and up to two 100Base-FX optical Ethernet ports (shared)
  • Optional IEC 61850-9-2 sampling value and IEC 61850-8-1 GOOSE, MMS support
  • Supports IEC 61850, DNP3.0, IEC 60870-5-103 over TCP/IP; two RS-485 ports (IEC 60870-5-103) and RS-485 for clock sync; RS-232/RS-485 rear port for printer


User Interface
  • Front-panel HMI with large LCD and 9-button keypad
  • Front RJ-45 port for testing and setting
  • Rear serial port for printer; language selection (English + local language)
  • Configuration and analysis software: PCS-Explorer


Technical specifications
  • Model: PCS-902 line distance relay for overhead and underground transmission lines
  • Protection technologies: DPFC distance protection, power swing blocking (PSBR), SOTF, out-of-step, broken conductor, dead zone, thermal overload, pole discrepancy
  • Standards and protocols: IEC 61850-8-1 MMS/GOOSE, IEC 61850-9-2 SV; DNP3.0 and IEC 60870-5-103 supported
  • Ethernet: up to 4 x 10Base-T/100Base-TX copper; up to 2 x 100Base-FX optical (shared)
  • Optical pilot channels: optional single/dual fiber (G.703, C37.94)
  • Serial interfaces: RS-485 ports, RS-232/RS-485 printer port
  • Optional comm. module: 6 optical Ethernet ports for IEC 61850-9-2 and GOOSE
  • Time sync: IRIG-B, SNTP, PPS, PPM, IEEE 1588
  • Event/disturbance recording: event recorder and 32 disturbance records with COMTRADE waveforms
  • Applications: series-compensated lines, double-circuit, heavily loaded, weak-in-feed, short and long lines; single or dual-breaker schemes