Product Overview- Model: SP-PV-2/2
- Input: 2 strings
- Output: 2 strings
- Degree of Protection: IP65
- Installation method: Wall mounting
SummaryDC combiner box for photovoltaic arrays integrating a surge protection device (SPD). Provides overvoltage protection, DC switching and fusing for two input strings and two outputs in a wall-mount IP65 enclosure with LED status indication.
Technical Parameters (table)Model No: SPPV/2/2
DC Surge Arrester: SPSP-D2 (EN 50539 Type 2)
Max. Operation / Rated Working Voltage (Ucpv / Ui): 1000 V DC
Max. Discharge Current: 40 kA
Max. DC Short-Circuit Current per Input (Isc): 15 A (changeable)
Rated / Maximum Current Output (Ie): 32 A
Enclosure: SP24PN, Material: Polycarbonate / ABS, Impact Rating: IK10
Degree of Protection: IP65
DC Fuse Holder: SPOPV-32B & SPOPV-30; Fuse Link: 10×38 mm, 15 A
Cable Glands: Input PG09 (2.5–16 mm²), Output PG21 (2.5–16 mm²)
DC Switch / Disconnector: SP DS1-DB / S32 / 4R
Standards: EN 50539 Type 2, IEC 60947-3
Operating Temperature: -20 °C to +60 °C, Humidity up to 99%, Altitude up to 2000 m
Dimensions (W×H×D): 292 × 220 × 132 mm
Additional VisualsIncludes product photograph and wiring/connection diagram showing 2-in / 2-out topology and internal component locations for installation and wiring guidance.
Characteristics / technical specifications- Model: SP-PV-2/2
- Application: Combiner box for DC photovoltaic arrays (2 strings)
- Integrated surge protection device (SPD): SPSP-D2, EN 50539 Type 2
- Rated operation voltage: 1000 V DC
- Max. discharge current (Imax): 40 kA
- Max. DC short-circuit current per input: 15 A (fusible / configurable)
- Rated output current: 32 A
- Enclosure material: Polycarbonate / ABS, IP65, IK10
- Fuse holders: SPOPV-32B & SPOPV-30; recommended fuse 10×38 mm, 15 A
- Cable entries: PG09 (input), PG21 (output), 2.5–16 mm²
- Mounting: Wall mounting
- Standards & certifications: EN 50539 Type 2, IEC 60947-3, TUV, CE
- Operating range: -20 °C to +60 °C; humidity up to 99%; up to 2000 m altitude