PRODUCT OVERVIEWSP-JXF low-voltage distribution box is designed for three-phase 3-, 4- and 5-wire systems up to 400 V or for load currents up to 630 A. It provides centralized control and protection functions including leakage protection, motor overload, short-circuit and phase-loss protection. The enclosure is modular, compact and available in multiple material and mounting configurations for indoor or outdoor installations across power generation, rail, aerospace, petrochemical, metallurgy, textile, real estate and steel industries.
COMPLIANCE WITH STANDARDS- GB/T 7251.12-2013 Low-voltage Switchgear and Controlgear Assemblies – Part 2: Power Assemblies
- IEC 61439-1 Low-voltage Switchgear and Controlgear Assemblies – Part 1: General rules
- GB 10233 Basic testing method for low-voltage switchgear and controlgear assemblies
- GB17625.1-2003 EMC — Limits for harmonic current emissions (equipment input current per phase ≤ 16 A)
- GB 16838-2005 Environmental test methods and severities for fire electronic products
- GB 4208 Degrees of protection provided by enclosures (IP code)
- GB50171-2002 Code for construction and acceptance of switchboard outfit and secondary circuit equipment installation
- GB14287.1~3-2005 Alarm and control system for electric fire prevention
TECHNICAL CHARACTERISTICS AND ADVANTAGES- Surface protection
- High-voltage electrostatic epoxy powder coating for uniform finish.
- Typical coating thickness 60–80 μm (±20 μm); salt spray resistance up to 168 h.
- Available materials: cold-rolled steel, stainless steel, ABS, PC; standard color RAL7035 or customizable.
- Reliable electrical connection scheme
- Customized busbars for miniature and power breakers to meet temperature-rise and clearance requirements.
- System wiring uses national-standard conductors; copper bars processed by CNC for high precision.
- Cold-press terminals and advanced assembly procedures ensure secure conductor-to-component connections.
- Design verification — 7+5 comprehensive test standards
- Design verification according to IEC 61439-1.
- Structure inspection vs. performance inspection.
- Structure checks: 1- strength of materials and parts; 2- protection class of complete equipment; 3- electrical clearance and creepage distances; 4- integrity of protection against electric shock and protection circuits; 5- combination of switching devices and components; 6- internal circuit and connection; 7- external terminals.
- Performance checks: 1- dielectric properties; 2- verification of temperature rise; 3- short-circuit withstand strength; 4- electromagnetic compatibility; 5- mechanical operation.
ENVIRONMENTAL CONDITIONS FOR USE- Ambient temperature: -25°C to +40°C (24 h average ≤ +35°C). Capacity reduction required outside these limits.
- Maximum altitude: 2000 m.
- Relative humidity: ≤ 50% at +40°C (higher humidity allowed at lower temperatures; consider condensation).
- Installation tilt: ≤ 5° from vertical.
- Install away from severe vibration, shock or corrosive atmospheres; consult manufacturer for special environments.
TECHNICAL PARAMETERSTechnical parameters | SP-JXF
Rated current (A) | 630
Rated insulation voltage Ui (V AC) | 690
Rated operating voltage (V AC) | 400
Rated impulse withstand voltage (kV) | 8
Frequency (Hz) | 50
Rated short-time withstand current Icw (kA/1 s) | 20
IP protection degree | ≤ IP65
Operation | Indoor / Outdoor
Maximum altitude (m) | 2000
Average ambient temperature (°C) | 35
Pollution degree | 3
Box material | Cold-rolled steel, stainless steel, ABS, PC
Coating | Electrostatic epoxy powder
Color | RAL7035 (customizable)
Insulation material | High-temperature resistant, flame-retardant
OUTLINE AND INSTALLATION DIMENSIONSP-JXF typical outline examples (H × W × D, mm):
2520/14 | 250 × 200 × 140
3025/14 | 300 × 250 × 140
3025/18 | 300 × 250 × 180
3030/14 | 300 × 300 × 140
3030/18 | 300 × 300 × 180
4030/14 | 400 × 300 × 140
4030/20 | 400 × 300 × 200
Additional standard variants available per specification tables.
ORDERING INSTRUCTION- Specify model (SP-JXF variant).
- Indicate installation method (wall-mounted, floor-mounted, kiosk, etc.).
- Specify structure form and outline/dimension variant.
- Provide system diagram and control schematic where applicable; state any customization requirements.
CHARACTERISTICS / SPECIFICATIONS- Model: SP-JXF
- Rated current: 630 A
- Rated operating voltage: 400 V AC
- Rated insulation voltage Ui: 690 V AC
- Rated impulse withstand voltage: 8 kV
- Rated short-time withstand current Icw (1 s): 20 kA
- Frequency: 50 Hz
- IP protection: up to IP65
- Operating environment: indoor/outdoor, altitude ≤ 2000 m
- Box materials: cold-rolled steel, stainless steel, ABS, PC
- Coating: electrostatic epoxy powder, standard RAL7035 (customizable)
- Insulation: high-temperature resistant, flame-retardant materials