OverviewJet fans are used to control and extract smoke and harmful gases in car parks, and for daily ventilation. VENCO VRJ radial jet fans operate at lower speeds to remove CO and vehicle emissions during normal operation and at higher speeds to limit smoke spread in fire situations, enabling faster evacuation and safer access for emergency services. Tested to EN 12101-3, these units help maintain visibility for firefighters up to approximately 10 m.
Features- Available in 50 N and 100 N thrust models to reduce the number of units required
- Backward-curved impeller design reduces air turbulence
- Compact radial layout suitable for height-restricted car parks
- Tested and approved at 300°C for 2 hours according to EN 12101-3
- Electric motor with IP55 degree of protection and H class insulation
- 400 V, 3-phase, 50 Hz motor
Technical specifications- Application: Extraction of smoke and harmful gases in car parks; daily ventilation and smoke control in fire events
- Test standard: EN 12101-3; tested and approved at 300°C for 2 hours
- Thrust models: 50 N and 100 N
- Impeller: Backward-curved radial blades to reduce turbulence
- Suitable for: Height-restricted car parks
- Motor: 400 V, 3-phase, 50 Hz
- Motor protection: IP55
- Insulation class: H
- Operating modes: Low speed for CO and exhaust gas removal during daily use; high speed to limit smoke spread during fire
- Performance benefit: Improves visibility for firefighters up to approx. 10 m, accelerating response and limiting damage